New structure for three-phase, four-wires shunt active filter

被引:0
作者
Lamich, M. [1 ]
Balcells, J. [1 ]
Gonzalez, D. [1 ]
Gago, J. [1 ]
机构
[1] Univ Politecn Cataluna, Dept Elect Engn, Terrassa 08222, Spain
来源
2007 COMPATIBILITY IN POWER ELECTRONICS | 2007年
关键词
active filters; power conditioning; control of harmonic distortion;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents a new structure and control method for three phase four wires LC coupled parallel active power filters (APF) for harmonies cancellation. The main differential point with regard to other structures used in the past consists of the connection of neutral wire to negative of DC bus in the inverter, thus avoiding the need of split capacitors at the DC bus. The LC coupling and a particular control of the DC voltage at the coupling capacitor allow the use of low voltage at the DC bus and provide a symmetry of available voltage, in the current controller, during ton and t(off). The paper includes a general discussion of the new structure, comparing it with the classical L coupled shunt APFs and presents the control method to obtain the above mentioned voltage symmetry, which allows lower DC bus voltage and lower values of coupling L. Simulation and experimental results are given to show the behavior of the system, used for harmonies cancellation.
引用
收藏
页码:156 / 162
页数:7
相关论文
共 20 条