Experimental evaluation of a direct air-cooled lithium bromide-water absorption prototype for solar air conditioning

被引:53
|
作者
Gonzalez-Gil, A. [1 ,2 ]
Izquierdo, M. [1 ,2 ]
Marcos, J. D. [3 ]
Palacios, E. [4 ]
机构
[1] Inst Ciencias Construcc Eduardo Torroja CSIC, Madrid 28033, Spain
[2] UC3M, Escuela Politecn Super, Madrid 28911, Spain
[3] UNED, Escuela Tecn Super Ingn Ind, Madrid 28040, Spain
[4] UPM, Escuela Univ Ingn Tecn Ind, Madrid 28012, Spain
关键词
Absorption; Lithium bromide; Direct air-cooled; Solar cooling; Prototype; Experiment; OF-THE-ART; COOLING SYSTEM; VERTICAL TUBE; FALLING FILM; PERFORMANCE; BUILDINGS; CHILLER; VAPOR;
D O I
10.1016/j.applthermaleng.2011.06.019
中图分类号
O414.1 [热力学];
学科分类号
摘要
A new direct air-cooled single-effect LiBr-H2O absorption prototype is described and proposed for use in solar cooling. As distinguishing aspects, it presents: an adiabatic absorber using flat-fan sheets: an air-cooling system that directly refrigerates both the condenser and the absorber and; the possibility of being operated also as a double-effect unit. A solar facility comprising a 48 m(2) field of flat-plate collectors was used to test the single-effect operation mode of the prototype. Results from an experimental campaign carried out in Madrid during summer 2010 are shown and operation parameters corresponding to two typical summer days are detailed. The prototype worked efficiently, with COP values around 0.6. Cooling power varied from 2 kW to 3.8 kW, which represented about 85% of the prototype's nominal capacity. Chilled water temperatures mostly ranged between 14 degrees C and 16 degrees C, although the lowest measured value was of 12.8 degrees C. Condensation and absorption temperatures were under 50 degrees C and 46 degrees C, respectively, even with outdoor temperatures of 40 degrees C. Driving water temperature ranged between 85 degrees C and 110 degrees C. As a mean, the system was able to meet 65% of the cooling demand corresponding to a room of 40 m(2). No signs of crystallization were observed during about a hundred hours of operation. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:3358 / 3368
页数:11
相关论文
共 50 条
  • [1] Experimental comparison of two solar-driven air-cooled LiBr/H2O absorption chillers: Indirect versus direct air-cooled system
    Lizarte, R.
    Izquierdo, M.
    Marcos, J. D.
    Palacios, E.
    ENERGY AND BUILDINGS, 2013, 62 : 323 - 334
  • [2] Experimental studies on an air-cooled two-stage NH3-H2O solar absorption air-conditioning prototype
    Du, S.
    Wang, R. Z.
    Lin, P.
    Xu, Z. Z.
    Pan, Q. W.
    Xu, S. C.
    ENERGY, 2012, 45 (01) : 581 - 587
  • [3] Air-cooled LiBr-water absorption chillers for solar air conditioning in extremely hot weathers
    Kim, D. S.
    Ferreira, C. A. Infante
    ENERGY CONVERSION AND MANAGEMENT, 2009, 50 (04) : 1018 - 1025
  • [4] A solar-assisted hybrid air-cooled adiabatic absorption and vapor compression air conditioning system
    Chen, Erjian
    Chen, Jinfeng
    Jia, Teng
    Zhao, Yao
    Dai, Yanjun
    ENERGY CONVERSION AND MANAGEMENT, 2021, 250
  • [5] Experimental investigation on the performance of a solar powered lithium bromide-water absorption cooling system
    Li, Ming
    Xu, Chengmu
    Hassanien, Reda Hassanien Emam
    Xu, Yongfeng
    Zhuang, Binwei
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2016, 71 : 46 - 59
  • [6] Evaluation of air-cooled solar absorption cooling systems
    Kim, DS
    Machielsen, CHM
    PROCEEDINGS OF THE INTERNATIONAL SORPTION HEAT PUMP CONFERENCE, 2002, : 117 - 123
  • [7] Experimental results of a direct air-cooled ammonia-lithium nitrate absorption refrigeration system
    Llamas-Guillen, S. U.
    Cuevas, R.
    Best, R.
    Gomez, V. H.
    APPLIED THERMAL ENGINEERING, 2014, 67 (1-2) : 362 - 369
  • [8] Air conditioning using an air-cooled single effect lithium bromide absorption chiller:: Results of a trial conducted in Madrid in August 2005
    Izquierdo, M.
    Lizarte, R.
    Marcos, J. D.
    Gutierrez, G.
    APPLIED THERMAL ENGINEERING, 2008, 28 (8-9) : 1074 - 1081
  • [9] Appropriate heat load ratio of generator for different types of air cooled lithium bromide-water double effect absorption chiller
    Li, Zeyu
    Liu, Jinping
    ENERGY CONVERSION AND MANAGEMENT, 2015, 99 : 264 - 273
  • [10] Comparison of absorption refrigeration cycles for efficient air-cooled solar cooling
    Xu, Z. Y.
    Wang, R. Z.
    SOLAR ENERGY, 2018, 172 : 14 - 23