Experimental evaluation of a direct air-cooled lithium bromide-water absorption prototype for solar air conditioning

被引:53
作者
Gonzalez-Gil, A. [1 ,2 ]
Izquierdo, M. [1 ,2 ]
Marcos, J. D. [3 ]
Palacios, E. [4 ]
机构
[1] Inst Ciencias Construcc Eduardo Torroja CSIC, Madrid 28033, Spain
[2] UC3M, Escuela Politecn Super, Madrid 28911, Spain
[3] UNED, Escuela Tecn Super Ingn Ind, Madrid 28040, Spain
[4] UPM, Escuela Univ Ingn Tecn Ind, Madrid 28012, Spain
关键词
Absorption; Lithium bromide; Direct air-cooled; Solar cooling; Prototype; Experiment; OF-THE-ART; COOLING SYSTEM; VERTICAL TUBE; FALLING FILM; PERFORMANCE; BUILDINGS; CHILLER; VAPOR;
D O I
10.1016/j.applthermaleng.2011.06.019
中图分类号
O414.1 [热力学];
学科分类号
摘要
A new direct air-cooled single-effect LiBr-H2O absorption prototype is described and proposed for use in solar cooling. As distinguishing aspects, it presents: an adiabatic absorber using flat-fan sheets: an air-cooling system that directly refrigerates both the condenser and the absorber and; the possibility of being operated also as a double-effect unit. A solar facility comprising a 48 m(2) field of flat-plate collectors was used to test the single-effect operation mode of the prototype. Results from an experimental campaign carried out in Madrid during summer 2010 are shown and operation parameters corresponding to two typical summer days are detailed. The prototype worked efficiently, with COP values around 0.6. Cooling power varied from 2 kW to 3.8 kW, which represented about 85% of the prototype's nominal capacity. Chilled water temperatures mostly ranged between 14 degrees C and 16 degrees C, although the lowest measured value was of 12.8 degrees C. Condensation and absorption temperatures were under 50 degrees C and 46 degrees C, respectively, even with outdoor temperatures of 40 degrees C. Driving water temperature ranged between 85 degrees C and 110 degrees C. As a mean, the system was able to meet 65% of the cooling demand corresponding to a room of 40 m(2). No signs of crystallization were observed during about a hundred hours of operation. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:3358 / 3368
页数:11
相关论文
共 31 条
[1]   Design and experimental testing of the performance of an outdoor LiBr/H2O solar thermal absorption cooling system with a cold store [J].
Agyenim, Francis ;
Knight, Ian ;
Rhodes, Michael .
SOLAR ENERGY, 2010, 84 (05) :735-744
[2]  
[Anonymous], 2009, ASHRAE Handbook|Fundamentals
[3]   Experimental evaluation of the performances of a H2O-LiBr absorption refrigerator under different service conditions [J].
Asdrubali, F ;
Grignaffini, S .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2005, 28 (04) :489-497
[4]   Solar air conditioning in Europe - an overview [J].
Balaras, Constantinos A. ;
Grossman, Gershon ;
Henning, Hans-Martin ;
Infante Ferreira, Carlos A. ;
Podesser, Erich ;
Wang, Lei ;
Wiemken, Edo .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2007, 11 (02) :299-314
[5]   Absorption of water vapour in the falling film of water-(LiBr plus LiI+LiNO3+LiCl)in a vertical tube at air-cooling thermal conditions [J].
Bourouis, M ;
Vallès, M ;
Medrano, M ;
Coronas, A .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2005, 44 (05) :491-498
[6]   Comparative study of different solar cooling systems for buildings in subtropical city [J].
Fong, K. F. ;
Chow, T. T. ;
Lee, C. K. ;
Lin, Z. ;
Chan, L. S. .
SOLAR ENERGY, 2010, 84 (02) :227-244
[7]   Solar assisted air conditioning of buildings - an overview [J].
Henning, Hans-Martin .
APPLIED THERMAL ENGINEERING, 2007, 27 (10) :1734-1749
[8]   Air conditioning using an air-cooled single effect lithium bromide absorption chiller:: Results of a trial conducted in Madrid in August 2005 [J].
Izquierdo, M. ;
Lizarte, R. ;
Marcos, J. D. ;
Gutierrez, G. .
APPLIED THERMAL ENGINEERING, 2008, 28 (8-9) :1074-1081
[9]   Crystallization as a limit to develop solar air-cooled LiBr-H2O absorption systems using low-grade heat [J].
Izquierdo, M ;
Venegas, M ;
Rodríguez, P ;
Lecuona, A .
SOLAR ENERGY MATERIALS AND SOLAR CELLS, 2004, 81 (02) :205-216
[10]   Air conditioning in the region of Madrid, Spain: An approach to electricity consumption, economics and CO2 emissions [J].
Izquierdo, M. ;
Moreno-Rodriguez, A. ;
Gonzalez-Gil, A. ;
Garcia-Hernando, N. .
ENERGY, 2011, 36 (03) :1630-1639