Simulation-based optimization of heating and cooling seasonal performances of an air-to-air heat pump considering operating and design parameters using genetic algorithm

被引:23
作者
Lee, Sang Hun [1 ]
Jeon, Yongseok [1 ]
Chung, Hyun Joon [1 ]
Cho, Wonhee [1 ]
Kim, Yongchan [1 ]
机构
[1] Korea Univ, Dept Mech Engn, Seoul 136713, South Korea
关键词
Heat pump; SEER; SCOP; Neural network; Genetic algorithm; NEURAL-NETWORK ANALYSIS; HORIZONTAL TUBES; REFRIGERANT CHARGE; MODEL; FLOW; SYSTEM; CONDITIONER;
D O I
10.1016/j.applthermaleng.2018.08.078
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, a novel simulation model is developed to optimize the seasonal coefficient of performance (SCOP) and seasonal energy efficiency ratio (SEER) of air-to-air heat pumps under various operating and design parameters. The developed heat exchanger model is simplified using artificial neural networks. The operating and design parameters were optimized to maximize the SEER and SCOP according to the outdoor temperature using the genetic algorithm. The considered operating and design parameters included the compressor frequency, indoor air flow rate, outdoor air flow rate, peak load, and compressor volume. The SCOP and SEER with the optimization of all three operating parameters were 7.0% and 21.4% higher than those with the optimization of the compressor frequency, respectively. In addition, the maximum designed cooling peak load, which satisfied the SEER greater than 8.5, was 3.7 kW. Moreover, the maximum SCOP was observed at the designed heating peak load of 3.8 kW. Further, as the compressor volume increases by 37.2% and 22.8% over the baseline compressor volume, the SCOP and SEER increase by 3.8% and 1.1%, respectively.
引用
收藏
页码:362 / 370
页数:9
相关论文
共 42 条
[1]   Performance characteristics correlation for round tube and plate finned heat exchangers [J].
Abu Madi, M ;
Johns, RA ;
Heikal, MR .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1998, 21 (07) :507-517
[2]   Heating performance characteristics of a dual source heat pump using air and waste heat in electric vehicles [J].
Ahn, Jae Hwan ;
Kang, Hoon ;
Lee, Ho Seong ;
Jung, Hae Won ;
Baek, Changhyun ;
Kim, Yongchan .
APPLIED ENERGY, 2014, 119 :1-9
[3]  
[Anonymous], 1989, NISTIR 89-4133
[4]  
[Anonymous], 1975, 51 ASHRAE
[5]  
[Anonymous], 2013, 1912013 ANSIASME PTC
[6]  
[Anonymous], 2013, EN 14825--2013
[7]   Artificial neural network analysis of heat pumps using refrigerant mixtures [J].
Arcaklioglu, E ;
Erisen, A ;
Yilmaz, R .
ENERGY CONVERSION AND MANAGEMENT, 2004, 45 (11-12) :1917-1929
[8]   Performance parameters estimation of MAC by using artificial neural network [J].
Atik, Kemal ;
Aktas, Abdurrazzak ;
Deniz, Emrah .
EXPERT SYSTEMS WITH APPLICATIONS, 2010, 37 (07) :5436-5442
[9]   Sizing strategy of on-off and modulating heat pump systems based on annual energy analysis [J].
Bagarella, G. ;
Lazzarin, R. ;
Noro, M. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2016, 65 :183-193
[10]   Thermoeconomic analysis and optimization of residential split-type air conditioners [J].
Barreira, Eduardo M. ;
Negrao, Cezar O. R. ;
Hermes, Christian J. L. .
APPLIED THERMAL ENGINEERING, 2013, 50 (01) :629-636