Performance enhancement of gas turbine units by retrofitting with inlet air cooling technologies (IACTs): an hour-by-hour simulation study

被引:8
作者
Ahmadzadehtalatapeh, M. [1 ]
Rashidi, H. R. [1 ]
机构
[1] Chabahar Maritime Univ, Dept Mech & Marine Engn, Chabahar 9971756499, Iran
关键词
Gas turbine units; Inlet air cooling technologies (IACT); Output power; Performance; TRNSYS; POWER-PLANT; IMPROVEMENT; SYSTEMS;
D O I
10.1007/s40430-020-2216-7
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
In the present research, a yearly performance of a gas turbine unit and the unit with the added inlet air cooling technologies (IACTs) was investigated in terms of performance and output power using TRNSYS software. The existing system was retrofitted with five different IACTs, namely Config. A: existing system integrated with an evaporative media, Config. B: existing system integrated with a fogging unit, Config. C: existing system integrated with a mechanical chiller, Config. D: existing system integrated with an absorption chiller, and Config. E: existing system integrated with a thermal energy storage. The configurations were examined to determine the most proper configuration. The study revealed that Config. C was superior and was the optimal configuration for the gas turbine unit and it was recommended for the existing system. The study showed that Config. C was capable of enhancing the yearly output power with about 10.62%. After determining the proper configuration, a method benefiting a passive energy technology of heat pipe structure was also proposed. In the proposed method, a water-to-air heat pipe heat exchanger (HPHX) consisting of single heat pipe tubes was planned to be added to Config. C as a pre-cooling equipment. To this end, the mathematical performance of the water-to-air HPHX was derived to be defined in TRNSYS studio. It was shown that a considerable amount of energy could be obtained after adding the water-to-air HPHX to Config. C. The exergy analysis also proved that application of IACT improves the exergy efficiency of the whole system.
引用
收藏
页数:29
相关论文
共 35 条
[1]   Impact of the use of a hybrid turbine inlet air cooling system in arid climates [J].
Al-Ansary, Hany A. ;
Orfi, Jamel A. ;
Ali, Mohamed E. .
ENERGY CONVERSION AND MANAGEMENT, 2013, 75 :214-223
[2]   A review of inlet air-cooling technologies for enhancing the performance of combustion turbines in Saudi Arabia [J].
Al-Ibrahim, Abdulrahman M. ;
Varnham, Abdulhadi .
APPLIED THERMAL ENGINEERING, 2010, 30 (14-15) :1879-1888
[3]   Augmentation of gas turbine performance using air coolers [J].
Alhazmy, MM ;
Najjar, YSH .
APPLIED THERMAL ENGINEERING, 2004, 24 (2-3) :415-429
[4]   Performance and economic of the thermal energy storage systems to enhance the peaking capacity of the cas turbines [J].
Ameri, M ;
Hejazi, SH ;
Montaser, K .
APPLIED THERMAL ENGINEERING, 2005, 25 (2-3) :241-251
[5]  
[Anonymous], THERMODYNAMICS TRANS
[6]  
[Anonymous], TRNSYS 16 TRANS SYST
[7]   Performance improvement of gas turbine power plants by utilizing turbine inlet air-cooling (TIAC) technologies in Riyadh, Saudi Arabia [J].
Baakeem, Saleh S. ;
Orfi, Jamel ;
Al-Ansary, Hany .
APPLIED THERMAL ENGINEERING, 2018, 138 :417-432
[8]   Enhancement of gas turbine power output using earth to air heat exchanger (EAHE) cooling system [J].
Barakat, S. ;
Ramzy, Ahmed ;
Hamed, A. M. ;
El Emam, S. H. .
ENERGY CONVERSION AND MANAGEMENT, 2016, 111 :137-146
[9]   Techno-economic analysis of gas turbine inlet air cooling for combined cycle power plant for different climatic conditions [J].
Barigozzi, Giovanna ;
Perdichizzi, Antonio ;
Gritti, Carolina ;
Guaiatelli, Lacopo .
APPLIED THERMAL ENGINEERING, 2015, 82 :57-67
[10]   Gas turbine inlet air cooling system for enhancing propane recovery in a gas plant: Theoretical and cost analyses [J].
Bin Shams, Mohamed ;
Elkanzi, E. M. ;
Ramadhan, Zakareya ;
Rahma, Sadiq ;
Khamis, Mohamed .
JOURNAL OF NATURAL GAS SCIENCE AND ENGINEERING, 2017, 43 :22-32