ANALYTICAL CALCULATION OF WET COOLING TOWER PERFORMANCE WITH LARGE COOLING RANGES

被引:0
作者
Yilmaz, Alper [1 ]
机构
[1] Cukurova Univ, Dept Mech Engn, Fac Engn & Architecture, TR-01330 Balcali, Turkey
关键词
Cooling tower; Cooling range; Analytical solution; Numerical calculation; COUNTER-FLOW; DESIGN;
D O I
暂无
中图分类号
O414.1 [热力学];
学科分类号
摘要
Cooling tower performance calculations are usually performed numerically. In this paper, a simple differential equation for counter flow wet cooling tower is solved analytically taking into consideration the non-linear dependency of the saturated air enthalpy on temperature. The method allows analytical calculation of cooling tower performance with large cooling ranges. The analytically obtained values are compared with the well-known logarithmic mean enthalpy method (LMED) and corrected LMED method. It is seen that analytically obtained values are much more accurate than the values obtained using these two methods. The analytical results are also compared with experimental ones and it is seen that there is a good agreement between them.
引用
收藏
页码:45 / 56
页数:12
相关论文
共 12 条
[1]  
ASHRAE, 2001, AM SOC HEAT REFR AIR
[2]   Experimental investigation of the performance of a counter-flow, packed-bed mechanical cooling tower [J].
Bedekar, SV ;
Nithiarasu, P ;
Seetharamu, KN .
ENERGY, 1998, 23 (11) :943-947
[3]  
BERLINER P, 1975, KUHLTURME GRUNDLAGEN
[4]   A modified analysis of counter flow wet cooling towers [J].
ElDessouky, HTA ;
AlHaddad, A ;
AlJuwayhel, F .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1997, 119 (03) :617-626
[5]   Application of a general non-dimensional mathematical model to cooling towers [J].
Halasz, B .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 1999, 38 (01) :75-88
[6]   Design of Cooling Towers by the Effectiveness-NTU Method [J].
Jaber, H. ;
Webb, R. L. .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1989, 111 (1-4) :837-843
[7]   Performance characteristics of counter flow wet cooling towers [J].
Khan, JUR ;
Yaqub, M ;
Zubair, SM .
ENERGY CONVERSION AND MANAGEMENT, 2003, 44 (13) :2073-2091
[8]   A critical investigation into the heat and mass transfer analysis of counterflow wet-cooling towers [J].
Kloppers, JC ;
Kröger, DG .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2005, 48 (3-4) :765-777
[9]  
Kroger DG., 2004, Air-Cooled Heat Exchangers and Cooling Towers: Thermal-Flow Performance Evaluation and Design, V1-2
[10]  
Merkel F., 1925, Zeitschrift desvereines Dentscher Ingenieure, V70, P123