In-service diagnostic of polymeric insulators exposed to severe contamination

被引:0
作者
Hernandez-Corona, Ramiro [1 ]
Montoya-Tena, Gerardo [1 ]
机构
[1] IIE, Cuernavaca 62490, Morelos, Mexico
来源
2007 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA | 2007年
关键词
D O I
10.1109/CEIDP.2007.4451580
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In Mexico since 1995, polymeric insulators have been used in transmission lines exposed to severe contamination. Insulators from different manufacturers have been installed; however, some of them have failed during their early operation years. Consequently, since 2003, in-service diagnostic has been periodically carried out to identify high risk insulators, by using the visual corona and electric field measurement techniques. In this paper, the most important results obtained from different inspections performed in-service to polymeric insulators on Mexican transmission tines are presented. These results show that the visual corona and electric field measurement techniques can be used to identify high risk polymeric insulators prior to failure.
引用
收藏
页码:376 / 379
页数:4
相关论文
共 8 条
[1]  
FIEFFOCHAVEZ JL, 1996, IEE P-GENER TRANSM D, V143, P6
[2]  
FIERROCHAVEZ JL, 1999, ISH
[3]  
HACKAM R, 1999, IEEE T DIELECTRIC EL, V6
[4]  
HERNANDEZCORONA R, 2006, IEEE PES TRANSM DIST
[5]  
Linders M., 1999, ISH, V4, P439
[6]  
RAMIREZVAZQUEZ I, 2004, DIAGNOSTIC NONCERAMI
[7]  
THIONE L, 2000, OVERVIEW LIVE LINE D
[8]  
VILLANCOURT GH, 1997, 10 ISH