Study of annual performance and capacity of data center passive cooling mode

被引:5
作者
Sbaity, Ahmad Alamir [1 ]
Louahlia, Hasna [1 ]
Le Masson, Stephane [2 ]
机构
[1] Normandie Univ, Site Univ Bellevue, LUSAC Unicaen, 120 Rue Exode, F-50000 St Lo, France
[2] Orange Labs, Lannion, France
关键词
annual performance; data centers; modeling; passive cooling; thermosyphon; two-phase flow; 2-PHASE CLOSED THERMOSIPHON; WASTE HEAT; THERMAL PERFORMANCE; AIR; MANAGEMENT; SYSTEM; REFRIGERATION; RECOVERY; PIPE;
D O I
10.1002/er.7421
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This article studies a new architecture of a thermosyphon loop and its capacity to cool data center considering the climate of several cities in France. A parametric experimental study is carried out to show the effect of the refrigerant fill ratio, the input heat load, and the outside temperature. The optimal fill ratio is 16% and the maximum cooling capacity is 1900 W when the data center outside temperature is 20 degrees C. A hydraulic and thermal analytical model is developed to simulate the thermosyphon loop, and it is validated with the experimental results. The cooling load of a typical data center with ten racks, each one dissipates 4.5 kW, is simulated by TRNSYS software for the eight chosen cities in France. The annual performance shows that the percentage of undissipated heat is 13.4% in Marseille that has the highest annual average outside temperature and 2.7% in Caen that has the lowest summer average outside temperature of the data center. The particularity of this work is that it gives the annual performance of a new architecture of a thermosyphon loop in several cities of France with different climates and without electricity consumption.
引用
收藏
页码:4204 / 4221
页数:18
相关论文
共 50 条
  • [21] Thermal performance of residential building with mixed-mode and passive cooling strategies: The Brazilian context
    Eli, L. G.
    Krelling, A. F.
    Olinger, M. S.
    Melo, A. P.
    Lamberts, R.
    ENERGY AND BUILDINGS, 2021, 244
  • [22] Impacts of Local Cooling Technologies on Air Cooled Data Center Server Performance: Test Data Analysis of Heatsink, Direct Liquid Cooling and Passive 2-Phase Enhanced Air Cooling Based on Loop Heat Pipe
    Vuckovic, Maxime
    Depret, Nicolas
    2016 32ND THERMAL MEASUREMENT, MODELING & MANAGEMENT SYMPOSIUM (SEMI-THERM), 2016, : 71 - 80
  • [23] Combined Cooling and Power Supply in Data Center Park Toward Superconducting Energy Network
    Que, Yuqiao
    Yu, Yaoyao
    Mao, Zejing
    Wang, Boyan
    Tang, Miangang
    Chen, Xiaoyuan
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2024, 34 (08)
  • [24] Thermal Performance Evaluation of a Data Center Cooling System under Fault Conditions
    Cho, Jinkyun
    Park, Beungyong
    Jeong, Yongdae
    ENERGIES, 2019, 12 (15)
  • [25] Passive two-phase cooling of air circuit breakers in data center power distribution systems
    Robinson, A. J.
    Colenbrander, J.
    Byrne, G.
    Burke, P.
    McEvoy, J.
    Kempers, R.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2020, 121
  • [26] Study on the performance and free cooling potential of a R32 loop thermosyphon system used in data center
    Zou, Sikai
    Zhang, Quan
    Yue, Chang
    Wang, Jiaqiang
    Du, Sheng
    ENERGY AND BUILDINGS, 2022, 256
  • [27] Energy performance evaluation in a data center with water-side free cooling
    Mi, Ranran
    Bai, Xuelian
    Xu, Xin
    Ren, Fei
    ENERGY AND BUILDINGS, 2023, 295
  • [28] Thermodynamic Performance Assessment of Air Conditioner Combining Evaporative and Passive Cooling
    Gupta, Sunil Kumar
    Arora, B. B.
    Arora, Akhilesh
    JOURNAL OF THERMAL SCIENCE AND ENGINEERING APPLICATIONS, 2024, 16 (05)
  • [29] Study of the performance of passive cooling strategies in buildings under arid weather conditions
    Kazeoui, Habiba
    Tahakourt, Abdelkader
    Bourbia, Sofiane
    JOURNAL OF MATERIALS AND ENGINEERING STRUCTURES, 2023, 10 (03): : 461 - 476
  • [30] Two-phase liquid-immersion data center cooling system: Experimental performance and thermoeconomic analysis
    Kanbur, Baris Burak
    Wu, Chenlong
    Fan, Simiao
    Tong, Wei
    Duan, Fei
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 118 : 290 - 301