Active Islanding Detection Using High-Frequency Signal Injection

被引:144
作者
Diaz Reigosa, David [1 ]
Briz, Fernando [1 ]
Blanco Charro, Cristian [1 ]
Garcia, Pablo [1 ]
Manuel Guerrero, Juan [1 ]
机构
[1] Univ Oviedo, Dept Elect & Comp Syst Engn, Gijon 33204, Spain
关键词
Active islanding detection; grid impedance measurement; high-frequency signal injection; power system monitoring; SELECTIVE HARMONIC COMPENSATION; POWER; GENERATION; DESIGN;
D O I
10.1109/TIA.2012.2209190
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Islanding detection is of great importance for reliable operation of smart grids. Islanding-detection methods can be classified into three different groups, i.e., active, passive, and communication-based methods. Active methods inject a disturbing signal (typically a voltage) and analyze the system response (typically in the current). These techniques have a low nondetection zone (NDZ) but present the inconvenience inherent to injecting a disturbing signal. Passive methods monitor the grid condition from the grid variables. These techniques are easy to implement but present a large NDZ. Communication methods have the inconvenience of relying on communications, currently being of limited use. This paper proposes a new active islanding-detection method, based on the measurement of the grid high-frequency impedance by means of the injection of a high-frequency voltage. The advantages of the method are almost negligible adverse effects due to the injected high-frequency voltage and accurate and fast islanding detection, i.e., in the range of a few milliseconds. Furthermore, the estimated high-frequency impedance can be used for the adaptive control of the power converter.
引用
收藏
页码:1588 / 1597
页数:10
相关论文
共 23 条
[1]  
[Anonymous], 503301 EUR EN
[2]  
[Anonymous], 2004, 61727 IEC
[3]  
[Anonymous], 2000, 9292000 IEEE
[4]  
[Anonymous], DK 5940 CRIT CONN GE
[5]  
[Anonymous], 012611 DINVDE
[6]   A digital controlled PV-inverter with grid impedance estimation for ENS detection [J].
Asiminoaei, L ;
Teodorescu, R ;
Blaabjerg, F ;
Borup, U .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2005, 20 (06) :1480-1490
[7]  
Asiminoaei L, 2004, APPL POWER ELECT CO, P1527
[8]  
Bower W., 2002, SAND20023591 SAND NA
[9]  
Briz F, 2011, IEEE ENER CONV, P2892, DOI 10.1109/ECCE.2011.6064158
[10]   On-line grid impedance estimation based on harmonic injection for grid-connected PV inverter [J].
Ciobotaru, Mihai ;
Teodorescu, Remus ;
Blaabjerg, Frede .
2007 IEEE INTERNATIONAL SYMPOSIUM ON INDUSTRIAL ELECTRONICS, PROCEEDINGS, VOLS 1-8, 2007, :2437-+