On-line monitoring of partial discharges on stator windings of large rotating machines in the petrochemical environment

被引:7
作者
Bethge, A [1 ]
Lo, PKW
Phillipson, JT
Weidner, JR
机构
[1] Siemens AG, D-13629 Berlin, Germany
[2] Imperial Oil Ltd, Prod & Chem Div, Sarnia, ON N7T 7M5, Canada
[3] Exxon Chem Co, Southampton SO45 1TX, Hants, England
[4] Siemens AG, D-45466 Mulheim, Germany
关键词
machines; on-line monitoring; partial discharges;
D O I
10.1109/28.739022
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This paper describes a joint collaboration program between a major large machine manufacturer and a petrochemical manufacturer to investigate the effectiveness of time- and frequency-domain techniques for on-line monitoring of the health of high-voltage machine stator insulation systems. Information is given on the factory and site testing carried out, as well as on the analysis and discussion of the results. It is concluded that both techniques can be used in the petrochemical environment for general assessments, but the time-domain technique is required if identification of specific locations of discharge sites is needed.
引用
收藏
页码:1359 / 1365
页数:7
相关论文
共 16 条
  • [1] Burnley K. G., 1990, 6th INSUCON 1990 BEAMA International Electrical Insulation Conference, P345
  • [2] GEARY R, 1990, P IEEE INT S EL INS, P141
  • [3] GRUNEWALD P, 1996, 4 INT C GEN MOT PART
  • [4] HOLBOLL JT, 1994, P ICEM 94 PAR FRANC, V2, P68
  • [5] *INT EL COMM, 1981, PUBL INT EL COMM, V270
  • [6] James R. E., 1990, Journal of Electrical and Electronics Engineering, Australia, V10, P338
  • [7] KREUGER FH, 1970, ELECTRA, P61
  • [8] LANGER J, 1995, ETG FACHT TIEL EL IS, P201
  • [9] LO P, 1992, P IEEE IAS PETR CHEM, P177
  • [10] PEMEN AJM, 1994, IEEE 1994 ANNUAL REPORT - CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, P118, DOI 10.1109/CEIDP.1994.591724