Experimental study and steady-state model of a novel plate loop heat pipe without compensation chamber for CPU cooling

被引:30
作者
Du, Sheng [1 ]
Zhang, Quan [1 ]
Hou, Peilin [1 ]
Yue, Chang [1 ]
Zou, Sikai [1 ]
机构
[1] Hunan Univ, Coll Civil Engn, Changsha 410082, Hunan, Peoples R China
基金
中国国家自然科学基金;
关键词
Loop heat pipe; Liquid line wick; Cycle operating performance; Temperature distribution; Steady-state model of LHP; THERMAL PERFORMANCE; WICK;
D O I
10.1016/j.scs.2019.101894
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this study, a new type of loop heat pipe (LHP) without compensation chamber is designed and manufactured, meanwhile the liquid line is fitted with a sintered wick to enhance startup and steady operation capacity. Specifically, the thermal characteristics of the LHP are studied experimentally. The results show that the LHP can start up smoothly at any heat load and the highest temperature of LHP does not exceed 90 degrees C. The fluid at the liquid line is subcooled, which is beneficial for the startup and steady operation of LHP. When the heat load is in range of 10 W to 50 W, the LHP works at variable conductance mode, and the system thermal resistance and the loop thermal resistance both decrease sharply with the increasing heat load. When the heat load is in range of 50 W to 150 W, the LHP enters a constant conductance mode, and the system thermal resistance and the loop thermal resistance remain basically constant. Besides, the steady-state model of LHP used to predict the operating temperature of LHP is established. The simulation results were compared with the experimental data, and the maximum relative error of evaporator, vapor, condenser outlet and liquid line wick inlet temperature are less than 15%.
引用
收藏
页数:8
相关论文
共 25 条
[1]  
[Anonymous], 2018, CHINA ACAD INFORM CO
[2]   Mathematical modeling of steady-state operation of a loop heat pipe [J].
Bai, Lizhan ;
Lin, Guiping ;
Zhang, Hongxing ;
Wen, Dongsheng .
APPLIED THERMAL ENGINEERING, 2009, 29 (13) :2643-2654
[3]   Economic analysis of data center cooling strategies [J].
Cho, Kyuman ;
Chang, Hyunjae ;
Jung, Yongho ;
Yoon, Yoojung .
SUSTAINABLE CITIES AND SOCIETY, 2017, 31 :234-243
[4]  
Chuang P.-Y.A., 2003, An Improved Steady-State Model of Loop Heat Pipe Based on Experimental and Theorical Analyses
[5]  
Eduard O., 2018, SUSTAINABLE CITIES S, V36, P185
[6]   The study of servers' arrangement and air distribution strategy under partial load in data centers [J].
Jin, Chaoqiang ;
Bai, Xuelian .
SUSTAINABLE CITIES AND SOCIETY, 2019, 49
[7]   Experimental investigation of wraparound loop heat pipe heat exchanger used in energy efficient air handling units [J].
Jouhara, Hussam ;
Meskimmon, Richard .
ENERGY, 2010, 35 (12) :4592-4599
[8]   Experimental study on the loop heat pipe with a planar bifacial wick structure [J].
Joung, Wukchul ;
Yu, Taeu ;
Lee, Jinho .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2008, 51 (7-8) :1573-1581
[9]  
Kaya T, 1999, 37 AER SCI M EXH
[10]   Analytical Model for Characterization of Loop Heat Pipes [J].
Launay, Stephane ;
Sartre, Valerie ;
Bonjour, Jocelyn .
JOURNAL OF THERMOPHYSICS AND HEAT TRANSFER, 2008, 22 (04) :623-631