A higher order interior point method to minimize active power loss in electric energy systems

被引:3
|
作者
Rider, MJ [1 ]
Paucar, VL [1 ]
Garcia, AV [1 ]
Bedriñana, MF [1 ]
机构
[1] State Univ Campinas, UNICAMP, Dept Elect Energy Syst, Campinas, SP, Brazil
关键词
active power loss minimization; competitive electric markets; interior point method; nonlinear programming; optimal power flow;
D O I
10.1109/LESCPE.2003.1204702
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this paper the active power loss minimization problem is formulated as an optimal power now (OPF), including equality and inequality nonlinear constraints which represent the power system security conditions. The OPF has been solved using the multiple predictor-corrector interior point method, of the family of higher order interior point methods, enhanced with an optimal computation of the step length. The optimal computation of the primal and dual step sizes minimizes the primal and dual objective function errors, respectively, assuring a continuous decrease of the errors during the iterations of the interior point method. The proposed methodology has been applied to minimize the active power loss of IEEE-30, IEEE-57, IEEE-118 and IEEE-300 bus test systems. Test results indicated that the convergence is facilitated and the number of iterations may be small.
引用
收藏
页码:189 / 193
页数:5
相关论文
共 50 条
  • [31] Controlled Charging of Electric Vehicles to Minimize Energy Losses in Distribution Systems
    Mousavi, S. M.
    Flynn, Damian
    IFAC PAPERSONLINE, 2016, 49 (27): : 324 - 329
  • [32] Tidal energy in electric power systems
    Sheth, S
    Shahidehpour, M
    2005 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS, 1-3, 2005, : 630 - 635
  • [33] A Modified Higher Order Power Filter for Grid-Connected Renewable Energy Systems
    Anzalchi, Arash
    Moghaddarni, Masood
    Moghaddasi, Arnir
    Pour, Maneli Malek
    Sarwat, Arif
    2016 IEEE/IAS 52ND INDUSTRIAL AND COMMERCIAL POWER SYSTEMS TECHNICAL CONFERENCE (I&CPS), 2016,
  • [34] Reactive Power Optimization in Transmission Power System Using Interior Point Method
    Rahiel, D.
    Mounir, K.
    Chaker, A.
    Haimour, R.
    INTERNATIONAL REVIEW OF ELECTRICAL ENGINEERING-IREE, 2010, 5 (02): : 614 - 618
  • [35] Power market oriented optimal power flow via an interior point method
    Xie, K
    Song, YH
    IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2001, 148 (06) : 549 - 556
  • [36] Active power flow safety correction control method of transmission sections based on a primal-dual interior point method
    Sun S.
    Yan W.
    Wu C.
    Liu Y.
    Yang B.
    Xu Z.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2021, 49 (07): : 75 - 85
  • [37] The problem of the active and reactive optimum power dispatching solved by utilizing a primal-dual interior point method
    Garzillo, A.
    Innorta, M.
    Ricci, M.
    International Journal of Electrical Power and Energy System, 1998, 20 (06): : 427 - 434
  • [38] Dynamic optimal power flow using interior point method and benders decomposition considering active and reactive constraints
    Yamin, H. Y.
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2006, 34 (12) : 1377 - 1393
  • [39] The problem of the active and reactive optimum power dispatching solved by utilizing a primal-dual interior point method
    Garzillo, A
    Innorta, M
    Ricci, M
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 1998, 20 (06) : 427 - 434