Dust contamination on surface of transmission line insulators in air-polluted regions in China: statistical characteristics, adhesion mechanism, and environmental impact factors

被引:7
作者
Jiang, Miao [1 ]
Guo, Jingrun [1 ]
Jiang, Yunpeng [2 ]
Li, Lee [1 ]
Lu, Ming [3 ]
机构
[1] Huazhong Univ Sci & Technol, Sch Elect & Elect Engn, State Key Lab Adv Electromagnet Engn & Technol, Wuhan 430074, Hubei, Peoples R China
[2] State Grid Zhejiang Hangzhou Xiaoshan Power Suppl, Hangzhou 311200, Zhejiang, Peoples R China
[3] State Grid Henan Elect Power Res Inst, Zhengzhou 450052, Henan, Peoples R China
基金
中国国家自然科学基金;
关键词
Dust contamination; Adhesion model; Environmental factors; Composite insulator; Size distribution; DER-WAALS FORCE; PARTICLE; CAPILLARY; CONTACT; MODELS;
D O I
10.1007/s11356-020-08692-6
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Dust particles suspended in the atmosphere have been a big headache for electric power transmission industry in China. As transmission lines pass through dusty or air-polluted areas, dust contaminants are likely to deposit and accumulate on line insulators, which is one of the greatest causes of flashover and failure of power transmission. To study the statistical characteristics of this type of contamination, dust samples were collected and measured, and a physical model was set up to explain the deposition and accumulation mechanism of the particles. The trajectories of particles were tracked using fluid mechanics and contact mechanics, and an adhesion criterion was proposed. Simulation software was then applied to validate the model; further different environmental factors were studied that would affect the particle size distribution. The results show that under natural contamination conditions, the particle size distribution on the surface of the insulator shows a certain concentration at size ranges 1 similar to 100 mu m and basically obeys a log-normal distribution. In addition, relative humidity, air velocity, and the charge accumulated on the surface all have significant influences on particle size distribution characteristics, while the effect of the electric field is mainly reflected in the difference in the number concentration of particle adhesion.
引用
收藏
页码:23643 / 23654
页数:12
相关论文
共 1 条
  • [1] Dust contamination on surface of transmission line insulators in air-polluted regions in China: statistical characteristics, adhesion mechanism, and environmental impact factors
    Miao Jiang
    Jingrun Guo
    Yunpeng Jiang
    Lee Li
    Ming Lu
    Environmental Science and Pollution Research, 2020, 27 : 23643 - 23654