Thermal performance of peripheral-finned tube evaporators under frosting

被引:8
作者
Timmermann, Marco A. S. [1 ]
Kaviany, Massoud [2 ]
Barbosa, Jader R., Jr. [1 ]
机构
[1] Univ Fed Santa Catarina, Dept Mech Engn, Polo Res Labs Emerging Technol Cooling & Thermoph, BR-88040900 Florianopolis, SC, Brazil
[2] Univ Michigan, Dept Mech Engn, Ann Arbor, MI 48109 USA
关键词
Peripheral finned-tube; Frost formation; Heat transfer enhancement; Heat exchanger; COLD FLAT SURFACE; HEAT-TRANSFER; SEMIEMPIRICAL CORRELATION; PRESSURE-DROP; PACKED-BEDS; PART I; MODEL; EXCHANGER; CONDUCTIVITY; OPTIMIZATION;
D O I
10.1016/j.ijheatmasstransfer.2017.09.008
中图分类号
O414.1 [热力学];
学科分类号
摘要
This study presents an experimental and theoretical evaluation of frost formation on the moist air side of a peripheral finned-tube (PFT) heat exchanger. Previous studies of this compact geometry correlated the friction and heat transfer parameters above the few-point temperature of the air (no frost or condensate formation). Here, for the first time, the thermal-hydraulic performance of a PFT heat exchanger is analyzed under frosting. A PFT heat exchanger prototype was evaluated experimentally in a closed-loop wind tunnel calorimeter to determine the influence of the tube wall temperature, air velocity and psychrometric properties (temperature and relative humidity) on the heat transfer rate, air-side pressure drop and frost buildup on the surface. The thermal and hydrodynamic behavior of the enhanced air-side surface was analyzed using a distributed heat exchanger model in which mass, momentum and energy balances are applied to one-dimensional control volumes in the air flow direction. The model treats the air flow path as a porous medium in which the porosity, equivalent particle diameter and thermal properties vary as a function of time due to the frost accumulation. Good agreements (within 20% average error) between the model predictions and the experiments for the air-side pressure drop and heat transfer rate have been found. The enthalpy effectiveness was found to drop from 0.68 for dry to 0.50 under severe frosting, which suggests that the PFT heat exchanger continues to be effective under frost. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:194 / 207
页数:14
相关论文
共 44 条
  • [1] Review of defrosting methods
    Amer, Mohammed
    Wang, Chi-Chuan
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2017, 73 : 53 - 74
  • [2] [Anonymous], PRINCIPLES ENHACED H
  • [3] Air-side heat transfer and pressure drop in spiral wire-on-tube condensers
    Barbosa, Jader R., Jr.
    Sigwalt, Rodrigo A.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2012, 35 (04): : 939 - 951
  • [4] FROST DEPOSITION ON COLD SURFACES
    BRIAN, PLT
    REID, RC
    SHAH, YT
    [J]. INDUSTRIAL & ENGINEERING CHEMISTRY FUNDAMENTALS, 1970, 9 (03): : 375 - &
  • [5] Modeling and performance analyses of fin-and-tube heat exchanger operating under frost conditions
    Chen, Yi-Guang
    Jiang, Qing-Yang
    Yang, Ji-Chun
    Hou, Jing-Xin
    Wu, Xiao-Yan
    [J]. INTERNATIONAL JOURNAL OF LOW-CARBON TECHNOLOGIES, 2017, 12 (02) : 162 - 170
  • [6] Experimental study of frost accumulation on fan-supplied tube-fin evaporators
    da Silva, Diogo L.
    Hermes, Christian J. L.
    Melo, Claudio
    [J]. APPLIED THERMAL ENGINEERING, 2011, 31 (6-7) : 1013 - 1020
  • [7] A mathematical model for frost growth and densification on flat surfaces
    El Cheikh, Amne
    Jacobi, Anthony
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2014, 77 : 604 - 611
  • [8] Combating Frosting with Joule-Heated Liquid-Infused Superhydrophobic Coatings
    Elsharkawy, Mohamed
    Tortorella, Domenico
    Kapatral, Shreyas
    Megaridis, Constantine M.
    [J]. LANGMUIR, 2016, 32 (17) : 4278 - 4288
  • [9] ERGUN S, 1952, CHEM ENG PROG, V48, P89
  • [10] HANDLEY D, 1968, TRANS INST CHEM ENG, V46, pT251