Shielding failure lightning protection of 500kV quadruple-circuit transmission lines on the same tower

被引:0
|
作者
Yu, Shifeng [1 ]
Ruan, Jiangjun [1 ]
机构
[1] Wuhan Univ, Sch Elect Engn, Wuhan 430072, Peoples R China
关键词
electric geometry model (EGM); ground obliquity; quadruple-circuit on the same tower; shielding failure; striking distance factor;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The paper analyzes the performance of shielding failure lightning protection of 500kV quadruple-circuit overhead ac transmission lines on the same tower with revised EGM method and discusses the shielding effect of ground wires to phase conductors. Calculating the shielding failure trip out rate and modeling reasonably based on the analysis of tower style. The relationships between trip out rate and the influence factors such as tower height, protection angle, ground obliquity and striking distance factor are achieved. A conclusion is drawn that the shielding failure rate will turn larger when tower height, protection angle, ground obliquity become larger and the striking distance factor becomes smaller. The calculation and analysis results show that negative protection angle and lower tower height are effective to improve the performance of shielding failure of 500kV quadruple-circuit transmission lines on the same tower.
引用
收藏
页码:1705 / 1708
页数:4
相关论文
共 50 条
  • [21] Analysis of ecological environment for 500kV four circuits power transmission lines on same tower
    Zhang, Bingyi
    Wang, Xiaohui
    Zhao, Min
    Zhao, Yisong
    Wang, Xiaoyan
    Feng, Guihong
    2006 INTERNATIONAL CONFERENCE ON POWER SYSTEMS TECHNOLOGY: POWERCON, VOLS 1- 6, 2006, : 764 - +
  • [22] Phase Arrangement for 500kV Quadruple Circuit Transmission Line in Indonesia
    Kusuma, Aristo Adi
    Pramana, Putu Agus Aditya
    Munir, Buyung S.
    2016 INTERNATIONAL CONFERENCE ON SMART GREEN TECHNOLOGY IN ELECTRICAL AND INFORMATION SYSTEMS (ICSGTEIS), 2016, : 33 - 37
  • [23] Assessment of Lightning Backflash Outage Rate of Quadruple-circuit Transmission Lines due to Subsequent Strokes
    Huang, Bo
    Fu, Zhengcai
    Jiang, Anfeng
    Wang, Guoli
    Li, Ruihai
    2014 INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2014, : 917 - 921
  • [24] Lightning performance of 500 kV double-circuit line on same tower of the Three Gorges outgoing lines
    Huang, Weigang
    Zhongguo Dianli/Electric Power, 2000, 33 (05): : 57 - 61
  • [25] Cross-voltage short-circuit calculation for mixed-voltage quadruple-circuit lines on the same tower
    Zheng, Tao
    Zhang, Jiaqin
    Wu, Dan
    Huang, Shaofeng
    Wang, Xiaoli
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (09) : 2342 - 2350
  • [26] Secure distance of the quadruple-circuit transmission line with vertical arrangements on the same tower passing over buildings
    Zhou, Hao
    Zhang, Xiao
    Zhao, Bin-Cai
    Dai, Pan
    Wu, Hao
    Wu, Zhe
    Gaodianya Jishu/High Voltage Engineering, 2009, 35 (12): : 3077 - 3085
  • [27] Research for the Maintenance Way of Partial Outage on 500kv/220 kV Four-circuit Mixed-voltage Transmission Lines on the Same Tower
    Li, Jinliang
    Wang, Zhigang
    Xia, Zengming
    Wang, Tiqing
    Zeng, Wenyuan
    Yan, Yu
    Yang, Qi
    Li, Wen
    Long, Chenhai
    Ren, Huisong
    2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,
  • [29] Design and Full-scale Test for Steel Tubular Tower of UHV and EHV Quadruple-Circuit Transmission Line on the Same Tower
    Li, Qinghua
    Yang, Jingbo
    Han, Junke
    THERMAL, POWER AND ELECTRICAL ENGINEERING, PTS 1 AND 2, 2013, 732-733 : 1045 - 1051
  • [30] Transverse differential protection for quadruple-circuit lines with asymmetrical parameters
    Liu, Qi
    Tai, Nengling
    Fan, Chunju
    Yu, Zhongan
    Shang, Jin
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2016, 31 (22): : 159 - 167