Comparison of test methods for shallow layered rock thermal conductivity between in situ distributed thermal response tests and laboratory test based on drilling in northeast China

被引:28
|
作者
Zhang, Yanjun [1 ,2 ]
Hao, Shuren [1 ]
Yu, Ziwang [1 ]
Fang, Jingtao [3 ]
Zhang, Jianing [1 ]
Yu, Xiaomin [4 ]
机构
[1] Jilin Univ, Coll Construct Engn, Changchun 130026, Jilin, Peoples R China
[2] Jilin Univ, Key Lab Groundwater Resource & Environm, Minist Educ, Changchun 130026, Jilin, Peoples R China
[3] Geol Survey Inst Liaoning Prov, Shenyang 110035, Liaoning, Peoples R China
[4] Hebei Bur Geol & Mineral Explorat, Geol Brigade 2, Tangshan 063000, Hebei, Peoples R China
关键词
Distributed thermal response test; Thermal conductivity; Laboratory test; Ground source heat pump; SOURCE HEAT-PUMPS; PERFORMANCE; SYSTEMS; SOILS; FIELD;
D O I
10.1016/j.enbuild.2018.06.009
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The development and utilization of shallow geothermal energy have rapidly improved worldwide. The thermal physical parameters of rock and soil layers must be accurately measured to design a ground source heat pump system. The obtained thermal conductivity of rock and soil play a critical role in optimizing heat pump system and cost-saving design. In this study, detailed tests were performed on a borehole in Jixi City, Heilongjiang Province in northeast China. In situ geotechnical comprehensive thermal conductivity and layered rock thermal conductivities were obtained by traditional thermal response test (TRT) and distributed thermal response test (DTRT), respectively. A series of laboratory tests were also conducted on rock samples obtained from drilling and the thermal conductivities were compared with that obtained through DTRT. Changes in groundwater environment, moisture content contribute to the deviation of the laboratory experimental results from the value derived through in situ test. The influence of different factors and the analytic hierarchy process (AHP) method was analyzed to determine the weight value for correcting the thermal conductivity tested in the laboratory. The accuracy of the layered conductivity obtained by DIRT, and laboratory test before and after modification was examined by the numerical model based on TOUGH2-MP code. The heat exchange power was predicted on the basis of thermal conductivity obtained by TRT (2.29 kW), DTRT (2.197 kW) and laboratory test before and after being corrected (1.917 kW and 2.180 kW, respectively). The proposed method was proven to be useful in determining layered rock thermal conductivity. (C) 2018 Elsevier B.V. All rights reserved.
引用
收藏
页码:634 / 648
页数:15
相关论文
共 5 条
  • [1] A Case Study of Field Thermal Response Test and Laboratory Test Based on Distributed Optical Fiber Temperature Sensor
    Ma, Yongjie
    Zhang, Yanjun
    Cheng, Yuxiang
    Zhang, Yu
    Gao, Xuefeng
    Shan, Kun
    ENERGIES, 2022, 15 (21)
  • [2] Estimation method of soil thermal conductivity distribution of coaxial vertical borehole heat exchanger based on distributed thermal response test
    Wang, Changlong
    Jiang, Tianzhuo
    Zhou, Xing
    Guo, Yanchun
    Huang, Xinjie
    Lu, Jinli
    RENEWABLE ENERGY, 2025, 238
  • [3] Comparison between new enhanced thermal response test methods for underground heat exchanger sizing
    Galgaro, A.
    Da Re, R.
    Carrera, A.
    Di Sipio, E.
    Dalla Santa, G.
    GEOMECHANICS FOR ENERGY AND THE ENVIRONMENT, 2024, 40
  • [4] TEST METHOD RESEARCH OF SOIL THERMAL CONDUCTIVITY OF GROUND SOURCE HEAT PUMP BASED ON THREE-DIMENSIONAL DISTRIBUTED THERMAL RESPONSE TEST HEAT TRANSFER MODEL
    Deng Z.
    Nian Y.
    Cheng W.
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2023, 44 (04): : 259 - 265
  • [5] Comparison of Thermal Conductivity and Long-Term Change of Building Insulation Materials According to Accelerated Laboratory Test Methods of ISO 11561 and EN 13166 Standard
    Kim, Jin-Hee
    Kim, Sang-Myung
    Kim, Jun-Tae
    Energies, 2024, 17 (23)