The influence of weak transverse magnetic field on plasma dissipation process in the post-arc phase in a vacuum interrupter

被引:1
|
作者
Shi, Qilin [1 ,2 ]
Wu, Hao [3 ]
Yuan, Zhao [1 ,2 ]
Tao, Zhe [1 ,2 ]
Li, Guixia [1 ,2 ]
Luo, Wei [1 ,2 ]
Jiang, Wei [3 ]
机构
[1] Huazhong Univ Sci & Technol, State Key Lab Adv Elect Engn & Technol, Wuhan 430074, Peoples R China
[2] Huazhong Univ Sci & Technol, Key Lab Pulsed Power Technol, Minist Educ, Wuhan 430074, Peoples R China
[3] Huazhong Univ Sci & Technol, Sch Phys, Wuhan 430074, Peoples R China
基金
中国国家自然科学基金;
关键词
vacuum circuit breakers; particle-in-cell; Monte Carlo collisions; transverse magnetic field; plasma; PARTICLE SIMULATION; CIRCUIT-BREAKERS; KINETIC-MODEL;
D O I
10.1088/2058-6272/ac4fb3
中图分类号
O35 [流体力学]; O53 [等离子体物理学];
学科分类号
070204 ; 080103 ; 080704 ;
摘要
Transverse magnetic field (TMF) contacts and applying external TMF are often adopted for reducing the ablation of the contact surface, but TMF will also affect the breaking performance of the vacuum interrupters. In this work, we investigated the influence of weak TMF on the expansion of the plasma in the post-arc phase with one-dimensional implicit particle-in-cell/Monte Carlo collision model, and we added an external circuit to the model to ensure the correctness of the calculation results. We simulated multiple magnetic field strengths (<30 mT), compared the plasma expansion process with the TMF strengths of 0 mT and 10 mT, and discussed the influence of metal vapor density on the insulation performance recovery of the vacuum interrupter. From the results, applying TMF with strength below 5 mT has little effect on the expansion of the plasma, and the TMF can increase the plasma density which improve the flow capacity of vacuum circuit breakers when the magnetic field above 10 mT, which is because the particles become more difficult to leave the discharge area under the force of the magnetic field. In general, we find that weak external TMF may adversely affect the breaking performance of the vacuum circuit breakers.
引用
收藏
页数:10
相关论文
共 50 条
  • [1] The influence of weak transverse magnetic field on plasma dissipation process in the post-arc phase in a vacuum interrupter
    石奇霖
    吴浩
    袁召
    陶哲
    李归霞
    罗威
    姜巍
    Plasma Science and Technology, 2022, (05) : 238 - 247
  • [2] The influence of weak transverse magnetic field on plasma dissipation process in the post-arc phase in a vacuum interrupter
    石奇霖
    吴浩
    袁召
    陶哲
    李归霞
    罗威
    姜巍
    Plasma Science and Technology, 2022, 24 (05) : 238 - 247
  • [3] The influence from the residual magnetic field on the plasma dissipation in the post-arc phase in a vacuum interrupter
    Wang, Haoran
    Zhou, Zhipeng
    Tian, Yunbo
    Wang, Zhenxing
    Liu, Zhiyuan
    Geng, Yingsan
    Wang, Jianhua
    2016 27TH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM (ISDEIV), VOL 2, 2016,
  • [4] Two-Dimensional Kinetic Simulation of the Post-Arc Plasma Dissipation Process of Vacuum Circuit Breaker Influenced by Transverse Magnetic Field
    Zhang, Yuanbing
    Ma, Hui
    Yu, Chen
    Fu, Chen
    Liu, Zhiyuan
    Geng, Yingsan
    Wang, Jianhua
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2024, 34 (08)
  • [5] Investigation of the rotating arc plasma generated in transverse magnetic field (TMF) contacts of vacuum interrupter
    Pavelescu, D
    Braic, V
    Gherendi, F
    Braic, M
    Nitu, C
    Balaceanu, M
    Dumitrescu, G
    Pavelescu, G
    Nitu, S
    Anghelita, P
    ISDEIV: XXITH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, VOLS 1 AND 2, PROCEEDINGS, 2004, 21 : 156 - 159
  • [6] Measurement of Electrode Surface Temperature and Post-Arc Current in Vacuum Interrupter
    Daibo, Akira
    Niwa, Yoshimitsu
    Sasaki, Yo
    Saito, Takuya
    Yoshida, Takeshi
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2024, 52 (09) : 4396 - 4401
  • [7] Expanding sheath in a bounded plasma in the context of the post-arc phase of a vacuum arc
    Sarrailh, P.
    Garrigues, L.
    Hagelaar, G. J. M.
    Sandolache, G.
    Rowe, S.
    Jusselin, B.
    Boeuf, J. P.
    JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2008, 41 (01)
  • [8] Post-arc current measurement and interruption performance of vacuum interrupter in DC interruption
    Tang, Qiang
    Jia, Shenli
    Shi, Zongqian
    Mo, Yongpeng
    JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2022, 55 (14)
  • [9] Research on post-arc reignition phenomena for 40.5kV vacuum interrupter
    Jing, Y
    Ma, ZY
    Li, J
    ISDEIV: XXITH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, VOLS 1 AND 2, PROCEEDINGS, 2004, 21 : 371 - 373
  • [10] Study on Post-Arc Current of DC Current Interruption Using Vacuum Interrupter
    Inagaki, Takashi
    Tokoyoda, Sho
    Sato, Motohiro
    Donen, Taiki
    2023 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, PESGM, 2023,