Study on the relationship between the characteristics of water droplets on the shed of composite insulators and the pollution flashover voltage

被引:7
作者
Wang, Wei [1 ]
Lu, Hailiang [1 ]
Li, Chun [1 ]
Deng, Yeqiang [1 ]
Lan, Lei [1 ]
Wen, Xishan [1 ]
Luo, Bing [2 ]
Xiao, Wei [2 ]
机构
[1] Wuhan Univ, Coll Elect Engn & Automat, Wuhan 430072, Peoples R China
[2] China Southern Power Grid Elect Power Res Inst, State Key Lab HVDC, Guangzhou 510663, Peoples R China
关键词
Composite insulator; Accelerated aging; Water droplet characteristics; Artificial smear; Pollution flashover voltage; SILICONE-RUBBER;
D O I
10.1016/j.egyr.2022.02.265
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The anti-pollution flashover characteristic of composite insulators is the main indicators to evaluate their electrical performance, and the pollution flashover voltage can directly characterize the anti-pollution flashover characteristics of the insulators. This paper proposed an on-line detection method for the pollution flashover voltage of composite insulators. Samples of composite insulator shed with different hydrophobicity were prepared by using NaOH solution with pH value of 13 and temperature of 80 degrees C. According to the distribution of water droplets on the surface of the sample, the characteristic parameter of the number of water droplets was proposed. The samples with different characteristic parameters were smear-stained and used for the pollution flashover voltage test. The relationships between the number of water droplets on the sample surface and the pollution flashover voltage and leakage current were obtained, which can provide guidance for the evaluation of the operation state of composite insulators. (c) 2022 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/). Peer-review under responsibility of the scientific committee of the 2021 The 2nd International Conference on Power Engineering, ICPE, 2021.
引用
收藏
页码:1071 / 1077
页数:7
相关论文
共 14 条
  • [1] Properties of Interfaces between Silicone Rubber and Epoxy
    Andersson, Johan
    Gubanski, Stanislaw M.
    Hillborg, Henrik
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (05) : 1360 - 1367
  • [2] Diffusion of low molecular weight siloxane from bulk to surface
    Homma, H
    Kuroyagi, T
    Izumi, K
    Mirley, CL
    Ronzello, J
    Boggs, SA
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1999, 6 (03) : 370 - 375
  • [3] Development of composite insulators in China
    Liang, XD
    Wang, SW
    Fan, J
    Guan, ZC
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1999, 6 (05) : 586 - 594
  • [4] Liu Yun-peng, 2010, High Voltage Engineering, V36, P2634
  • [5] Lu Li., 2019, STUDY MAGNETIC RESON
  • [6] AC and DC Corona/Ozone-induced Ageing of HTV Silicone Rubber
    Ma, Bin
    Gubanski, Stanislaw M.
    Hillborg, Henrik
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2011, 18 (06) : 1984 - 1994
  • [7] Ma Huancheng., 2017, RES INFLUENCE SURFAC
  • [8] Hydrophobicity transfer from silicone rubber to adhering pollutants and its effect on insulator performance
    Swift, D. A.
    Spellman, C.
    Haddad, A.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2006, 13 (04) : 820 - 829
  • [9] [王羽 Wang Yu], 2019, [中国电机工程学报, Proceedings of the Chinese Society of Electrical Engineering], V39, P3253
  • [10] [蒋兴良 Jiang Xingliang], 2018, [中国电机工程学报, Proceedings of the Chinese Society of Electrical Engineering], V38, P320