Accurate Location of Inter-Circuit Faults on Double-Circuit Transmission Lines Based on Sparse Wide-Area Voltage Measurements

被引:0
作者
Jiao, Xiangqing [1 ]
Liao, Yuan [1 ]
机构
[1] Univ Kentucky, Dept Elect & Comp Engn, Lexington, KY 40506 USA
来源
2017 IEEE POWER & ENERGY SOCIETY GENERAL MEETING | 2017年
关键词
Inter-circuit fault; fault location; short-circuit analysis; wide area measurements;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Inter-circuit fault is a type of fault in which phases from two or more circuits at a single geographical location are connected. This type of fault is more likely to occur on a double circuit transmission line located on a single tower structure. This paper proposes a location algorithm for inter-circuit faults on a double-circuit transmission line based on sparse wide-area voltage measurements. The proposed algorithm is based on bus impedance matrix theory. This method is applicable to both transposed and untransposed double-circuit transmission lines. Wide-area measurements are captured by phasor-measurement units (PMUs) from buses which may be far away from faulted line. The need of fault type information is eliminated, and distributed parameter transmission line model is adopted to fully consider shunt capacitances. The proposed method has been evaluated with simulation studies based on Electromagnetic Transients Program (EMTP). Quite accurate location results are yielded, and representative results are presented in the paper.
引用
收藏
页数:5
相关论文
共 19 条