A method and case study of thermal response test with unstable heat rate

被引:34
作者
Hu, Pingfang [1 ]
Meng, Qingfeng [1 ]
Sun, Qiming [1 ]
Zhu, Na [1 ]
Guan, Changsheng [2 ]
机构
[1] Huazhong Univ Sci & Technol, Sch Environm Sci & Engn, Wuhan 430074, Peoples R China
[2] Wuhan Univ Technol, Sch Engn & Architecture, Wuhan 430074, Peoples R China
基金
中国国家自然科学基金;
关键词
Variable-rate heat; Ground thermal properties; Unsteady state method; IN-SITU DETERMINATION; PERFORMANCE; EXCHANGERS; CONDUCTIVITY;
D O I
10.1016/j.enbuild.2012.01.036
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper proposed a new method based on modified composite model in the thermal response test (TRT) in the variable heat rate case study. The new method considered the unsteady-state heat transfer in the borehole instead of the line-source model assumption. A Matlab program was compiled which can perform inversion calculation to obtain the ground thermal properties. The superposition principle was used to process the variable-rate problem. This new method was applied to two thermal response tests. The simulation value based on the method shows a good agreement with the measurement data of water temperature. The proposed method would save the time and reduce the cost of TRT when power fluctuation or failure occurs. (C) 2012 Elsevier B.V. All rights reserved.
引用
收藏
页码:199 / 205
页数:7
相关论文
共 20 条
[1]  
Austin W., 2000, ASHRAE T, V106, P365
[2]  
Beier R.A., 2003, ASHRAE T, V109, P475
[3]  
BEIER R.A., 2003, ASHRAE Transactions, V109, P463
[4]  
Beier RA, 2005, ASHRAE TRAN, V111, P702
[5]   Equivalent time for interrupted tests on borehole heat exchangers [J].
Beier, Richard A. .
HVAC&R RESEARCH, 2008, 14 (03) :489-505
[6]  
Bixel H.C., 1967, SOC PET ENG J, V7, P301, DOI DOI 10.2118/1516-PA
[7]   Improvement in modeling of heat transfer in vertical ground heat exchangers [J].
Diao, NR ;
Zeng, HY ;
Fang, ZH .
HVAC&R RESEARCH, 2004, 10 (04) :459-470
[8]   In-situ thermal response test for ground source heat pump system in Elazig, Turkey [J].
Esen, Hikmet ;
Inalli, Mustafa .
ENERGY AND BUILDINGS, 2009, 41 (04) :395-401
[9]   First in situ determination of the thermal performance of a U-pipe borehole heat exchanger, in Cyprus [J].
Florides, Georglos ;
Kalogirou, Soteris .
APPLIED THERMAL ENGINEERING, 2008, 28 (2-3) :157-163
[10]   Multi-injection rate thermal response test in groundwater filled borehole heat exchanger [J].
Gustafsson, A. -M. ;
Westerlund, L. .
RENEWABLE ENERGY, 2010, 35 (05) :1061-1070