HIGH-RESISTANCE NEUTRAL GROUNDING IN INDUSTRIAL SYSTEMS AND THE GROUND FAULT PROTECTION

被引:0
|
作者
Bernardi, Gladston A. F. [1 ]
de Carvalho Filho, Jose Maria [1 ]
机构
[1] UNIFEI Univ Fed ltajuba, GQEE Grp Estudos Qualidade Energia Eletr, Itajuba, MG, Brazil
来源
2013 BRAZILIAN POWER ELECTRONICS CONFERENCE (COBEP) | 2013年
关键词
High-resistance neutral grounding; ground fault location and detection; charging current; sympathetic nuisance tripping;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The objective of this paper is to present the state-of-the art in the high-resistance neutral grounding practice in LV (480V) and MV (4.16kV) industrial power systems, not still widely known in Brazil, especially regarding the ground fault detection and location systems, and equipment protection with selectivity. This technique is important for the quality of energy and continuity of service in industrial processes. It is also presented a new synthesis for the range of adjustment of the ground-fault protection relays based on the constraints of the first ground-fault coexistence in the power supply system, the ground protection selectivity in the case of a second fault, the effective ground protection of equipment, and on the avoidance of nuisance tripping due to the charging current flow during faults. The possibility of using high-resistance neutral systems up to 4.16kV and beyond is discussed based on today's assumption of the limits of a self-sustainable carbonous arc in motor winding insulation failures and the calculation of charging currents.
引用
收藏
页码:1276 / 1282
页数:7
相关论文
共 50 条
  • [31] HIGH-RESISTANCE GROUDING OF 2400-VOLT DELTA SYSTEMS WITH GROUND-FAULT ALARM AND TRACEABLE SIGNAL TO FAULT
    FOX, FK
    GROTTS, HJ
    TIPTON, CH
    IEEE TRANSACTIONS ON INDUSTRY AND GENERAL APPLICATIONS, 1965, IGA1 (05): : 366 - &
  • [32] High Resistance Neutral Grounding
    Brusso, Barry
    Rifaat, Rasheek
    IEEE INDUSTRY APPLICATIONS MAGAZINE, 2012, 18 (01) : 10 - U5
  • [33] Grounding and ground fault protection of multiple generator installations on medium-voltage industrial and commercial power systems - Part 2: Grounding methods
    Pillai, P
    Pierce, A
    Bailey, B
    Douglas, B
    Mozina, C
    Normand, C
    Love, D
    Shipp, D
    Dalke, G
    Jones, JR
    Fischer, J
    Bowen, J
    Padden, L
    Powell, L
    Nichols, N
    Young, R
    Stringer, NT
    CONFERENCE RECORD OF THE 2003 ANNUAL PULP AND PAPER INDUSTRY TECHNICAL CONFERENCE, 2003, : 63 - 70
  • [34] IDENTIFYING GROUND-FAULT LOCATIONS Using adjustable speed drives in high-resistance grounded systems
    Wei, Lixiang
    Liu, Zhijun
    Kerkman, Russell J.
    Skibinski, Gary L.
    IEEE INDUSTRY APPLICATIONS MAGAZINE, 2013, 19 (02) : 47 - 55
  • [35] Analysis of distribution network line relay protection during single-phase high-resistance grounding faults in low resistance neutral grounded system
    Xu, Qingqiang
    Xu, Yang
    Zhou, Dongji
    Xi, Xuefeng
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2010, 34 (09): : 91 - 94
  • [36] Grounding fault protection based on fault resistance measurement for ineffectively earthed distribution systems
    School of Electrical and Information Engineering, Changsha University of Science and Technology, Changsha 410076, China
    不详
    Gaodianya Jishu, 2007, 1 (26-30): : 26 - 30
  • [38] High-Resistance Grounding Fault Location in High-Voltage Direct Current Transmission Systems Based on Deep Residual Shrinkage Network
    Huang, Ping
    Huang, Junlin
    Huang, Shengquan
    Yang, Guoting
    Wu, Zhipeng
    ELECTRONICS, 2025, 14 (03):
  • [39] APPLYING HIGH RESISTANCE NEUTRAL GROUNDING IN MEDIUM VOLTAGE SYSTEMS
    Kingrey, Lawrence J.
    Painter, Ralph
    Locker, Anthony S.
    2010 RECORD OF CONFERENCE PAPERS INDUSTRY APPLICATIONS SOCIETY 57TH ANNUAL PETROLEUM AND CHEMICAL INDUSTRY CONFERENCE PCIC, 2010,
  • [40] Selective High-Resistance Grounding System for a Cogeneration Facility
    Das, J. C.
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2015, 51 (06) : 5270 - 5280