Very fast transient overvoltages in GIS

被引:0
|
作者
Zhang, WY [1 ]
Shi, BZ [1 ]
Qiu, YC [1 ]
机构
[1] Xian Elect Power Coll, Xian, Peoples R China
来源
POWERCON '98: 1998 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY - PROCEEDINGS, VOLS 1 AND 2 | 1998年
关键词
fast transient; overvoltage; gas-insulated substation; insulation co-ordination;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A differentiating/integrating (D/I) system which does not change GIS configuration is developed for the measurement of very fast transient overvoltages (VFTO) occurring in GIS. Then the numerical computation of VFTO is studied on the base of field measurement results. Some factors influencing VFTO magnitude are analyzed through computation. The possible reason why VFTO may cause more failures in 330kV and above GIS is presented.
引用
收藏
页码:212 / 214
页数:3
相关论文
共 50 条
  • [1] Measurement of very fast transient overvoltages in GIS
    Shi, Baozhuang
    Zhang, Wenyuan
    Qiu, Yuchang
    Wang, Yun
    Dai, Youfu
    Gaodianya Jishu/High Voltage Engineering, 24 (01): : 17 - 18
  • [2] CAPACITIVE VOLTAGE SENSOR FOR MEASURING VERY FAST TRANSIENT OVERVOLTAGES IN GIS
    YASHIMA, M
    FUJINAMI, H
    TAKUMA, T
    ELECTRICAL ENGINEERING IN JAPAN, 1995, 115 (01) : 64 - 74
  • [3] Application of Multiple Modelling Techniques for Analysis of Very Fast Transient Overvoltages in GIS
    James, J.
    Albano, M.
    Haddad, A.
    Guo, D.
    2018 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2018,
  • [4] Analysis of Influential Factors in Determining Very Fast Transient Overvoltages of GIS Substations
    Babaei, Maziar
    Babaei, Mehdi
    Nourirad, Ghasem
    2014 IEEE 8TH INTERNATIONAL POWER ENGINEERING AND OPTIMIZATION CONFERENCE (PEOCO), 2014, : 79 - 84
  • [5] Effects of very fast transient overvoltages on transformer
    Shibuya, Y
    Fujita, S
    Shimomura, T
    IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1999, 146 (05) : 459 - 464
  • [6] Analysis of Very Fast Transient Overvoltages (VFTO) from Onsite Measurements on 800 kV GIS
    Li, Yunge
    Shang, Yong
    Zhang, Lin
    Shi, Rong
    Shi, Wei
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2012, 19 (06) : 2102 - 2110
  • [7] Measurement of Very Fast Transient Overvoltages at the Transformer Entrance
    Ma Guo-ming
    Li Cheng-rong
    Quan Jiang-tao
    Tang He-xiang
    Jiang Jian
    Yin Yong-hua
    Zhao Hong-guang
    Chao Hui
    ICEMS 2008: PROCEEDINGS OF THE 11TH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS, VOLS 1- 8, 2008, : 788 - +
  • [8] Computation of very fast transient overvoltages in transformer windings
    Popov, M
    van der Sluis, L
    Paap, GC
    De Herdt, H
    IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (04) : 1268 - 1274
  • [9] ACCURATE MODELLING OF VERY FAST TRANSIENT OVERVOLTAGES IN A 245kV GIS AND RESEARCH ON PROTECTION MEASURES
    Rao, J. V. G. Rama
    Amarnath, J.
    Kamakshaiah, S.
    2010 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTIC PHENOMENA, 2010,
  • [10] Very fast transient overvoltages in GIS with compressed SF6-N2 gas mixtures
    Singha, S
    Thomas, MJ
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2001, 8 (04) : 658 - 664