Internal flow numerical simulation of a cross-flow fan in refrigerant operating condition using user-defined functions

被引:2
作者
Xue, Yongfei [1 ,2 ]
Gan, Jiaye [2 ]
Wang, Jiabing [3 ]
Wu, Keqi [2 ,3 ]
机构
[1] Henan Inst Engn, Dept Civil Engn, Zhengzhou 450007, Henan, Peoples R China
[2] Huazhong Univ Sci & Technol, State Key Lab Coal Combust, Wuhan 430074, Hubei, Peoples R China
[3] Huazhong Univ Sci & Technol, Sch Energy & Power Engn, Wuhan 430074, Hubei, Peoples R China
关键词
UDF; cross-flow fan; air conditioner; internal and external flow characteristics; refrigerant operating condition; three-dimensional numerical simulation;
D O I
10.1002/fld.2226
中图分类号
TP39 [计算机的应用];
学科分类号
081203 ; 0835 ;
摘要
In the paper, a cross-flow fan in refrigerant operating condition is systematically simulated using user-defined functions. Three-dimensional simulations are acquired with Navier-Stokes equations coupled with k-epsilon turbulence model, and internal flow characteristics of an indoor split-type air conditioner are obtained, which is mainly composed of cross-flow fan and heat exchanger. It has systematically been simulated in the isothermal flow condition that the performance of cross-flow fan may be reduced easily with dry or humid air, and in the refrigerant operating condition in which user-defined functions are applied to the humid air, considered as a mixture of dry air and vapor. A density-modulated function is adopted to deal with the condensation of the vapor at the heat-transfer region approximately. The results show flow mechanism of the two gas-phase flow, including phase-vary process. The distribution of the parameters is not uniform at the inlet of the machine, the intensity and position of pressure and velocity vary along the axial direction of the fan, the distribution of vapor volume fraction and turbulent intensity in heat-transfer region is obtained, and the external characteristic data of the indoor machine are obtained and analyzed. Compared with the experimental data, the calculated characteristic curves and designed parameters are on target. (C) British Crown Copyright 2010/MOD. Reproduced with permission. Published by John Wiley & Sons, Ltd.
引用
收藏
页码:1039 / 1049
页数:11
相关论文
共 20 条
  • [1] CHEN CC, 1996, T CHINESE SOC AGR MA, V27, P30
  • [2] CHEN CC, 1995, T CHINESE SOC AGR MA, V126, P90
  • [3] Discrete noise prediction of variable pitch cross-flow fans by unsteady Navier-Stokes computations
    Cho, Y
    Moon, YJ
    [J]. JOURNAL OF FLUIDS ENGINEERING-TRANSACTIONS OF THE ASME, 2003, 125 (03): : 543 - 550
  • [4] FLUENT 6.2, 2005, FLUENT 6 2 UDF MAN
  • [5] Guo L., 2002, 2 PHASE MULTIPHASE F
  • [6] [胡俊伟 Hu Junwei], 2004, [机械工程学报, Chinese Journal of Mechanical Engineering], V40, P62
  • [7] LI QY, 1984, VENTILATOR
  • [8] [罗荣 Luo Rong], 2003, [流体机械, Fluid Machinery], V31, P19
  • [9] MING TZ, 2003, THESIS HUAZHONG U SC
  • [10] TUCKEY PR, 1982, INT C FAN DES APPL, P407