A pilot-based distance protection scheme for meshed distribution systems with distributed generation

被引:37
作者
Tsimtsios, Aristotelis M. [1 ]
Korres, George N. [2 ]
Nikolaidis, Vassilis C. [1 ]
机构
[1] Democritus Univ Thrace, Dept Elect & Comp Engn, GR-67100 Xanthi, Greece
[2] Natl Tech Univ Athens, Sch Elect & Comp Engn, Iroon Polytechniou 9, Athens 15780, Greece
关键词
Distance protection; Distributed generation; Meshed distribution system; Pilot protection; DISTRIBUTION NETWORKS; MICROGRID PROTECTION; OVERCURRENT RELAYS; COORDINATION; INTEGRATION; FEEDERS;
D O I
10.1016/j.ijepes.2018.08.022
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a pilot-based distance protection scheme for meshed distribution systems with a high penetration of distributed generation. The proposed scheme assumes distance relays installed at the opponent ends of each main line segment. A forward distance element is enabled in each relay to protect the main line segment, while, a reverse distance element is enabled in each relay for protecting adjacent buses and laterals. The relays protecting a main line segment or a bus/lateral communicate in a permissive logic, ensuring protection sensitivity and security at the same time. The scheme provides efficient primary and backup protection against faults of any type, even with a considerable fault resistance, and under weak-infeed conditions. It is also appropriate for both the grid-connected and the islanded mode of system operation. Coordination of the distance protection scheme with the lateral protection means is also addressed. Existing numerical distance relay technology is considered, to enhance the applicability of the proposed scheme. Offline setting of the distance relays is required, which has to be performed once. Only one setting group is ultimately extracted for each relay, suitable for different fault/system conditions, avoiding the need for adaptive protection techniques. The proposed scheme is applied to a test meshed distribution system and conclusions are drawn. Comparison with directional over-current and differential protection shows the advantages of the designed distance-based protection scheme.
引用
收藏
页码:454 / 469
页数:16
相关论文
共 51 条
[1]   An interior point method based protection coordination scheme for directional overcurrent relays in meshed networks [J].
Alam, Mahamad Nabab ;
Das, Biswarup ;
Pant, Vinay .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2016, 81 :153-164
[2]  
[Anonymous], 2014, IEEE Electrif. Mag
[3]  
[Anonymous], 2016, 2016 IEEE International Conference on Power System Technology (POWERCON)
[4]  
[Anonymous], 2011, NUMERICAL DISTANCE P
[5]  
[Anonymous], SAND201611210 SAND N
[6]  
[Anonymous], IEEE T SMART GRID
[7]  
[Anonymous], 2011, Integration of distributed generation in the power system
[8]  
[Anonymous], 1022519 EL POW RES I
[9]  
[Anonymous], 2012, NUMERICAL DIFFERENTI
[10]  
[Anonymous], 2017, 2017 IEEE INT C EL I