Three-dimensional FEM Electrical Field Calculation for FRP Hot Stick during EHV Live-line Work

被引:29
作者
Ghassemi, M. [1 ]
Farzaneh, M.
Chisholm, W. A.
机构
[1] Univ Quebec Chicoutimi, NSERC Hydroquebec UQAC Ind Chair Atmospher Icing, Chicoutimi, PQ G7H 2B1, Canada
关键词
Electrical field calculation; FRP hot stick; live-line work; flashover; freezing condition; FLASHOVER;
D O I
10.1109/TDEI.2014.004580
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In February and December 2012, SaskPower experienced two flashovers of "clean" Fiberglass-Reinforced Plastic (FRP) hot stick during cold weather live-line work under steady-state 230 kV ac system conditions. As for SaskPower, Manitoba Hydro had two separate live-line tool flashover events, in 1997 and 2002. Clean-fog tests and non-uniform wetting tests at Hydro-Quebec Research Institute (IREQ), and cold-fog tests at Kinectrics and UQAC were carried out to explain these flashovers. The laboratory tests demonstrated that inadvertent contamination of clean tools at a very light level (similar to 2-3 mu g cm(2)) of Equivalent Salt Deposit Density (ESDD) likely reduced voltage withstand capability of FRP hot sticks, particularly under freezing conditions. The flashover mechanism was identified when surfaces become fully wetted by the environment or surrounding fog. However, the source of moisture in field flashovers well below 0 degrees C, i.e. as low as -19 degrees C, was not identified. This study is based on laboratory tests and on using available pollution flashover models to explain the results. In this paper, the main objective is to determine the potential and electric field distribution along a FRP hot stick under dry condition and non-uniform wetting. A commercial software, COMSOL Multiphysics (TM), based on the finite element method (FEM), was used for the three-dimensional modeling and simulations. The results obtained will be useful to improve knowledge on the determination of discharge initiation conditions based on electric field distributions along a FRP hot stick.
引用
收藏
页码:2531 / 2540
页数:10
相关论文
共 26 条
[1]  
[Anonymous], 62073 IEC TS
[2]  
[Anonymous], 9781984 IEEE
[3]  
[Anonymous], D15011 ASTM
[4]   Failure analysis of extra-high voltage (EHV) hot sticks [J].
Booker, JR .
CONFERENCE RECORD OF THE 2004 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2004, :552-555
[5]  
Chisholm W. A., 2013, INMR WORLD C VANC 1
[6]   The cold-fog test [J].
Chisholm, WA ;
Ringler, KG ;
Erven, CC ;
Green, MA ;
Melo, O ;
Tam, Y ;
Nigol, O ;
Kuffel, J ;
Boyer, A ;
Pavasars, IK ;
Macedo, FX ;
Sabiston, JK ;
Caputo, RB .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (04) :1874-1880
[7]  
CIGRE, 2000, CIGRE MON, V158
[8]   PREDETERMINATION OF BEHAVIOUR OF POLLUTED INSULATORS [J].
CLAVERIE, P .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1971, PA90 (04) :1902-&
[9]  
Farzaneh M., 2013, ELECT FLASHOVER TEST
[10]   A Detailed Model for Discharge Initiation in Argon at Atmospheric Pressure in Presence of Dielectric Barriers [J].
Ghassemi, Mona ;
Mohseni, Hossein ;
Niayesh, Kaveh ;
Shayegani, Amir Abbas .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2012, 19 (03) :865-876