Acceptability of Three Transformer Hottest-Spot Temperature Models

被引:40
作者
Amoda, Oluwaseun A. [1 ]
Tylavsky, Daniel J. [1 ]
McCulla, Gary A. [2 ]
Knuth, Wesley A. [2 ]
机构
[1] Arizona State Univ, Tempe, AZ 85287 USA
[2] Salt River Project, Phoenix, AZ 85072 USA
关键词
Hottest-spot temperature; top-oil temperature; transformer; transformer thermal model; TOP-OIL TEMPERATURE; POWER TRANSFORMERS; THERMAL MODELS; PART I; PREDICTION; METRICS; HST;
D O I
10.1109/TPWRD.2011.2170858
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The acceptability of three transformer hottest-spot temperature (HST) models for use in dynamic loading are investigated and discussed in this paper. The hottest-spot models are the modified HST model, Swift's model, and Susa's model. The investigation fitted the models to measured field data obtained from utility transformers using numerical and statistical methods. Acceptability metrics to evaluate the models' accuracy, adequacy, and consistency in predicting HST were evaluated using results from the fitting procedures. These metrics serve as absolute measures to reveal any potential deficiencies in the models when they are used to build hottest-spot models for transformers using field data. The metrics also serve as relative measures to compare the performance of the models to one another. It is shown that the modified HST model and Susa's model are acceptable for implementing models from field data. And it is concluded that the Swift's model is not acceptable because it is structurally inaccurate.
引用
收藏
页码:13 / 22
页数:10
相关论文
共 21 条
[1]  
Amoda O., P 41 N AM POW S STAR, P1, DOI [10.1109/NAPS.2009.5484079, DOI 10.1109/NAPS.2009.5484079]
[2]  
Amoda O. A., 2008, P 40 N AM POW S C, P1
[3]  
[Anonymous], 2006, Introduction to Linear Regression Analysis
[4]  
[Anonymous], 2018, IEC 60076-7-2018
[5]  
[Anonymous], C57911995 IEEE
[6]   Prediction of top-oil temperature for transformers using neural networks [J].
He, Q ;
Si, JN ;
Tylavsky, DJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (04) :1205-1211
[7]   Acceptability of four transformer top-oil thermal models - Part II: Comparing metrics [J].
Jauregui-Rivera, Lida ;
Tylavsky, Daniel J. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (02) :866-872
[8]   Acceptability of four transformer top-oil thermal models - Part I: Defining metrics [J].
Jauregui-Rivera, Lida ;
Tylavsky, Daniel J. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (02) :860-865
[9]   An improved transformer top oil temperature model for use in an on-line monitoring and diagnostic system [J].
Lesieutre, BC ;
Hagman, WH ;
Kirtley, JL .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (01) :249-256
[10]   PREDICTING LIQUID-FILLED TRANSFORMER LOADING CAPABILITY [J].
PIERCE, LW .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1994, 30 (01) :170-178