Dynamic thermal performance analysis for fin-concrete ceiling in main control rooms of passive nuclear power plants

被引:5
作者
Huang, Yixiang [1 ]
Su, Xing [1 ]
Wu, Xiaoyan [1 ,2 ]
Ye, Wei [1 ,3 ]
Zhang, Xu [1 ]
机构
[1] Tongji Univ, Sch Mech Engn, Shanghai 200092, Peoples R China
[2] Jiaxing Univ, Coll Civil Engn & Architecture, Jiaxing 314001, Peoples R China
[3] Tongji Univ, Minist Educ, Key Lab Performance Evolut & Control Engn Struct, Shanghai 200092, Peoples R China
基金
中国国家自然科学基金;
关键词
Dynamic thermal performance; Passive cooling; Finned concrete; Thermal network model; COOLING SYSTEM; HEAT-PIPE; SIMULATION; INLEAKAGE; DESIGN; EXCHANGER;
D O I
10.1016/j.csite.2021.101402
中图分类号
O414.1 [热力学];
学科分类号
摘要
The main control rooms of passive nuclear plants must maintain a habitable environment once station-blackout accidents occur. In this condition, the heavy fin-concrete ceiling on the room will remove heat from kind of heat sources and protect from overheating environment. However, the dynamic thermal process of finned concrete ceiling has not been studied in various passive cooling measures. In this study, an efficient parametric resistance-capacitance thermal network model is established to describe dynamic thermal responses of heavy fin-concrete layer, and validated by dynamic temperature change data of a hot-box experiment for 24 h. Series indicators were deduced by analytic solutions. Based on the validated model and indicators, factor analysis was conducted to obtain details of effect of finned-plate geometric parameters and heat source intensity. The results show that initial 2-h thermal process can be divided into two stage, "transient stage" and "quasi-stable stage". The transient-stage thermal process is determined by source flux and finned coefficient of finned plate. The quasi-stable thermal process depends on thermal mass of the finned plate and heat source flux. Furthermore, there exists a linear relationship between air temperature and heat source flux. Finned plate layout can be design according to the factor assessment results.
引用
收藏
页数:16
相关论文
共 32 条
[21]   Westinghouse AP1000 advanced passive plant [J].
Schulz, T. L. .
NUCLEAR ENGINEERING AND DESIGN, 2006, 236 (14-6) :1547-1557
[22]   Numerical optimization of a finned tube bundle heat exchanger arrangement for passive spent fuel pool cooling to ambient air [J].
Unger, Sebastian ;
Krepper, Eckhard ;
Beyer, Matthias ;
Hampel, Uwe .
NUCLEAR ENGINEERING AND DESIGN, 2020, 361
[23]   An experimental investigation on the air-side heat transfer and flow resistance of finned short oval tubes at different tube tilt angles [J].
Unger, Sebastian ;
Beyer, Matthias ;
Arlit, Martin ;
Stasch, Philipp ;
Hampel, Uwe .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2019, 140 (225-237) :225-237
[24]   Numerical analysis of heat exchanger designs for passive spent fuel pool cooling to ambient air [J].
Unger, Sebastian ;
Krepper, Eckhard ;
Hampel, Uwe .
NUCLEAR ENGINEERING AND DESIGN, 2018, 333 :224-234
[25]  
US Nuclear Regulatory Commission, 2003, Demonstrating Control Room Envelope Integrity at Nuclear Power Reactors, Regulatory Guide 1.197
[26]   Experimental study on heat pipe heat removal capacity for passive cooling of spent fuel pool [J].
Xiong, Zhenqin ;
Wang, Minglu ;
Gu, Hanyang ;
Ye, Cheng .
ANNALS OF NUCLEAR ENERGY, 2015, 83 :258-263
[27]   Experimental study on the sub-atmospheric loop heat pipe passive cooling system for spent fuel pool [J].
Xiong, Zhenqin ;
Ye, Cheng ;
Wang, Minglu ;
Gu, Hanyang .
PROGRESS IN NUCLEAR ENERGY, 2015, 79 :40-47
[28]   The thermal performance of a loop-type heat pipe for passively removing residual heat from spent fuel pool [J].
Xiong, Zhenqin ;
Gu, Hanyang ;
Wang, Minglu ;
Cheng, Ye .
NUCLEAR ENGINEERING AND DESIGN, 2014, 280 :262-268
[29]   The design and simulation of a new spent fuel pool passive cooling system [J].
Ye, C. ;
Zheng, M. G. ;
Wang, M. L. ;
Zhang, R. H. ;
Xiong, Z. Q. .
ANNALS OF NUCLEAR ENERGY, 2013, 58 :124-131
[30]  
Zeng B., 2012, EXPT SIMULATION STUD