Frequency domain based DC fault analysis for bipolar HVDC grids

被引:24
作者
Wang, Mian [1 ]
Beerten, Jef [1 ]
Van Hertem, Dirk [1 ]
机构
[1] Katholieke Univ Leuven, EnergyVille Electa Res Grp, Elect Engn Dept ESAT, B-3001 Heverlee, Belgium
关键词
HVDC grids; DC grid protection; Travelling wave; Frequency domain analysis; Transfer function; PROTECTION;
D O I
10.1007/s40565-017-0307-y
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a frequency domain based methodology to analyse the influence of High Voltage Direct Current (HVDC) configurations and system parameters on the travelling wave behaviour during a DC fault. The method allows us to gain deeper understanding of these influencing parameters. In the literature, the majority of DC protection algorithms essentially use the first travelling waves initiated by a DC fault for fault discrimination due to the stringent time constraint in DC grid protection. However, most protection algorithms up to now have been designed based on extensive time domain simulations using one specific test system. Therefore, general applicability or adaptability to different configurations and system changes is not by default ensured, and it is difficult to gain in-depth understanding of the influencing parameters through time domain simulations. In order to analyse the first travelling wave for meshed HVDC grids, voltage and current wave transfer functions with respect to the incident voltage wave are derived adopting Laplace domain based component models. The step responses obtained from the voltage transfer functions are validated by comparison against simulations using a detailed model implemented in PSCAD (TM). Then, the influences of system parameters such as the number of parallel branches, HVDC grid configurations and groundings on the first travelling wave are investigated by analysing the voltage and current transfer functions.
引用
收藏
页码:548 / 559
页数:12
相关论文
共 21 条
[1]   WAVE-PROPAGATION CHARACTERISTICS OF CABLES [J].
AMETANI, A .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (02) :499-505
[2]  
[Anonymous], EMTDC US GUID V4 6
[3]  
[Anonymous], 2013, B452 CIGR
[4]  
[Anonymous], 2013, THESIS
[5]   A Fast Local Bus Current-Based Primary Relaying Algorithm for HVDC Grids [J].
Azad, Sahar Pirooz ;
Van Hertem, Dirk .
IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (01) :193-202
[6]  
Boeck DS, 2013, P 2013 IEEE POW EN S
[7]  
Davidson CC, 2015, P 11 IET INT C AC DC
[8]   Wavelet-based protection strategy for DC faults in multi-terminal VSC HVDC systems [J].
De Kerf, K. ;
Srivastava, K. ;
Reza, M. ;
Bekaert, D. ;
Cole, S. ;
Van Hertem, D. ;
Belmans, R. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2011, 5 (04) :496-503
[9]  
Hafner J, 2011, P CIGR BOL S BOL IT
[10]  
Hertem VD, 2011, P CIGR BOL S BOL IT