Analysis and control of bridge-type fault current limiter integrated with the dynamic voltage restorer

被引:15
作者
Tu, Chunming [1 ]
Guo, Qi [1 ]
Jiang, Fei [2 ]
Shuai, Zhikang [1 ]
He, Xi [1 ]
机构
[1] Hunan Univ, Natl Elect Power Convers & Control Engn Technol R, Changsha 410082, Hunan, Peoples R China
[2] Changsha Univ Sci Ea Technol, Sch Elect & Informat Engn, Changsha 410004, Hunan, Peoples R China
基金
中国国家自然科学基金;
关键词
Dynamic voltage restorer (DVR); Protection of power grid; Bridge-type fault current limiter (BFCL); Operation sequence; RECOVERY VOLTAGE; FILTER SYSTEM; DESIGN; FCL; QUALITY; CIRCUIT; DVR;
D O I
10.1016/j.ijepes.2017.08.031
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a novel bridge-type solid-state fault current limiter based on dynamic voltage restorer (BFCL-DVR). The new topology uses a DC-link in the back-to-back converter of DVR. The proposed BFCL-DVR is equivalent to the conventional DVR during normal operation mode. At fault inception, the controller deactivates the series converter IGBTs in faulty phase and activates the DC-link semiconductor switches, thus establishing an equivalent bridge-type current limiter to restrict the fault current. The magnitude of the fault current is adjustable by controlling the frequency and duty ratio of the semiconductor switch that is in parallel with the discharging resistance. Moreover, the device is able to quickly recover from the current limiting mode to the normal operation mode. In this study, the operation sequence, optimal value of discharging resistance, duty cycle, and frequency of semiconductor switches are obtained. The design methodology of the proposed BFCL-DVR is fully verified using PSCAD/EMTDC software. Experimental results validate the proposed topology and theoretical analysis. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:315 / 326
页数:12
相关论文
共 32 条
[1]   Survey of Solid-State Fault Current Limiters [J].
Abramovitz, Alexander ;
Smedley, Keuye Ma .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2012, 27 (06) :2770-2782
[2]  
Ambrish Chandra Vinod Khadkikarand, 2011, IEEE T POWER ELECTR, V26, P2414
[3]   Fundamental characteristics of superconducting fault current limiter using LC resonance circuit [J].
Arai, H. ;
Inaba, M. ;
Ishigohka, T. ;
Tanaka, H. ;
Arai, K. ;
Furuse, M. ;
Umeda, M. .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2006, 16 (02) :642-645
[4]   Test of resonance-type superconducting fault current limiter [J].
Arai, Kazuaki ;
Tanaka, Hideki ;
Inaba, Masaya ;
Arai, Hirohito ;
Ishigohka, Takeshi ;
Furuse, Mitsuho ;
Umeda, Masaichi .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2006, 16 (02) :650-653
[5]  
Behzad Naderi Seyed, 2013, IEEE T IDUSTRAL ELEC, V60
[6]   Integration of fault current limiters on power systems for voltage quality improvement [J].
Chang, CS ;
Loh, PC .
ELECTRIC POWER SYSTEMS RESEARCH, 2001, 57 (02) :83-92
[7]   Simulations and Tests of MCP-BSCCO-2212 Superconducting Fault Current Limiters [J].
de Sousa, W. T. B. ;
Polasek, A. ;
Silva, F. A. ;
Dias, R. ;
Jurelo, A. R. ;
de Andrade JR, R. .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2012, 22 (02)
[8]   Incorporating superconducting fault current limiters in the probabilistic evaluation of transient recovery voltage [J].
Faried, S. O. ;
Elsamahy, M. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2011, 5 (01) :101-107
[9]   A dual-functional bridge type FCL to restore PCC voltage [J].
Firouzi, M. ;
Gharehpetian, G. B. ;
Pishvaei, M. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2013, 46 :49-55
[10]   Development of a high-performance bridge-type fault current limiter [J].
Ghanbari, Teymoor ;
Farjah, Ebrahim ;
Zandnia, Amir .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2014, 8 (03) :486-494