Communication-Constrained Regionalization of Power Systems for Synchrophasor-Based Wide-Area Backup Protection Scheme

被引:34
作者
Zare, Javad [1 ]
Aminifar, Farrokh [1 ]
Sanaye-Pasand, Majid [1 ]
机构
[1] Univ Tehran, Sch Elect & Comp Engn, Coll Engn, Tehran 14395515, Iran
关键词
Communication latency; integer linear programming (ILP); system regionalization; wide-area backup protection (WABP);
D O I
10.1109/TSG.2014.2387051
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The evolving wide-area measurement system technology offers new opportunities for backup protection of transmission lines to avert the misoperation of conventional relays against system disturbances and prevent system instability. Since wide-area backup protection (WABP) is to operate at the range of a few hundred milliseconds, the delays associated with data and command communications and algorithm execution can be a troublesome issue in a large-scale power system. This paper briefly reviews a WABP scheme based on positive-sequence voltage phasor direct and indirect measurements. To overcome the problem of WABP delays, an integer linear programming (ILP) model is proposed to divide the power system into several protection regions. This process is accomplished in three stages in which the number and location of measurement devices (MDs), the number and boundary of protection regions, and the location of protection rooms, as well as the total number of communication links between MDs and protection rooms are optimized. The proposed WABP scheme is implemented in each region and individually protects the associated transmission lines. Execution of the proposed ILP model on different test systems reveals that with regionalization of the systems, WABP schemes can reliably be used in practice.
引用
收藏
页码:1530 / 1538
页数:9
相关论文
共 18 条
[1]   Wide area protection - Technology and infrastructures [J].
Adamiak, MG ;
Apostolov, AP ;
Begovic, MM ;
Heriville, CF ;
Martin, KE ;
Michel, GL ;
Phadke, AG ;
Thorp, JS .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (02) :601-609
[2]  
[Anonymous], 1999, POWER SYSTEMS TEST C
[3]  
[Anonymous], 2011, IEEEStandard C37.118.2-2011
[4]  
[Anonymous], 2012, 2012 ASIA PACIFIC PO
[5]   Smart Transmission Grid Applications and Their Supporting Infrastructure [J].
Bose, Anjan .
IEEE TRANSACTIONS ON SMART GRID, 2010, 1 (01) :11-19
[6]   Modeling and Simulation of Wide-Area Communication for Centralized PMU-Based Applications [J].
Chenine, Moustafa ;
Nordstrom, Lars .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (03) :1372-1380
[7]   Synchronized Phasor Measurement Applications in Power Systems [J].
De La Ree, Jaime ;
Centeno, Virgilio ;
Thorp, James S. ;
Phadke, A. G. .
IEEE TRANSACTIONS ON SMART GRID, 2010, 1 (01) :20-27
[8]   Wide-Area Backup Protection Algorithm Based on Fault Component Voltage Distribution [J].
He, Zhiqin ;
Zhang, Zhe ;
Chen, Wei ;
Malik, Om P. ;
Yin, Xianggen .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (04) :2752-2760
[9]  
IEEE, 2009, C37062009 IEEE
[10]  
Law YW, 2013, IEEE COMMUN MAG, V51, P34, DOI 10.1109/MCOM.2013.6400436