Evaluating the Impacts of Grounding Systems on Ground Currents and Transient Overvoltage

被引:5
作者
Saleh, Saleh A. [1 ]
Jewett, Danielle [1 ]
Al-Durra, Ahmed [2 ]
Kanukollu, Saikrishna [2 ]
Cardenas, Julian Luciano [1 ]
Valdes, Marcelo E. [3 ]
Panetta, Sergio A. R. [4 ]
机构
[1] Univ New Brunswick, Dept Elect & Comp Engn, Fredericton, NB E3B 5A3, Canada
[2] Khalifa Univ Sci Technol, Dept Elect & Comp Engn, Abu Dhabi 127788, U Arab Emirates
[3] ABB Elect Solut, Chapel Hill, NC 27517 USA
[4] I Gard Corp, Mississauga, ON L4T 1L2, Canada
关键词
Grounding system designs; power system grounding; power system ground faults; power system protection; PREVENT;
D O I
10.1109/TIA.2022.3190261
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This article presents a performance comparison of the solid, low impedance, high impedance, frequency-selective, and isolated grounding systems. A grounding system (for any power system component) is designed as an impedance ((Z) over bar (G)) that connects the neutral point to the ground. The impedance (Z) over bar (G) is constructed using a combination of R, L, and C elements. The values and combination type (series or parallel) ofR, L, and C determine the possible influence of (Z) over bar (G) on ground currents and potentials. Each grounding system is related to a system voltages level, a specific combination of R, L, and C, and a range of R, L, and C values. The solid, low impedance, high impedance, frequency-selective, and isolated grounding systems are designed for a 3 phi transformer and a 3f synchronous generator in order to compare their influences on ground currents and potentials during ground faults. The transformer and generator are tested for line-to-ground and double line-to-ground faults with all designed grounding systems. Test results show that some grounding systems can reduce ground currents only, while others can reduce ground potentials only. Such capabilities can be used to fulfill certain system and operation requirements (e.g., service continuity, ground capacity, etc.).
引用
收藏
页码:6002 / 6013
页数:12
相关论文
共 24 条
[1]  
[Anonymous], 2017, POWER SYSTEM TOOLBOX
[2]  
[Anonymous], 2018, IEEE Standard for Interconnection and Interoperability of DIstributed Energy Resources with Associated Electric Power Systems Interfaces
[3]  
[Anonymous], 2009, C629252009 IEEE
[4]   Influence of LV Neutral Grounding on Global Earthing Systems [J].
Cafaro, Giuseppe ;
Montegiglio, Pasquale ;
Torelli, Francesco ;
Barresi, Antonino ;
Colella, Pietro ;
De Simone, Angelo ;
Di Silvestre, Maria Luisa ;
Martirano, Luigi ;
Morozova, Elena Reizl ;
Napoli, Roberto ;
Parise, Giuseppe ;
Parise, Luigi ;
Pons, Enrico ;
Sanseverino, Eleonora Riva ;
Tommasini, Riccardo ;
Tummolillo, Filomena ;
Valtorta, Giovanni ;
Zizzo, Gaetano .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2017, 53 (01) :22-31
[5]   Analysis of Elevated Neutral-to-Earth Voltage in Distribution Systems With Harmonic Distortion [J].
Collins, Edward R. ;
Jiang, Jian .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (03) :1696-1702
[6]  
Digit, 2019, SIGN PROC CONTR ENG
[7]   Ground-fault currents in unit-connected generators with different elements grounding neutral [J].
Fulczyk, M ;
Bertsch, J .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2002, 17 (01) :61-66
[8]   Ground Fault Detection Method for Variable Speed Drives [J].
Guerrero, Jose Manuel ;
Navarro, Gustavo ;
Mahtani, Kumar ;
Platero, Carlos .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2021, 57 (03) :2547-2558
[9]  
IEEE Recommended Pract. for Protection and Coordination of Ind. and Commercial Power Syst. (IEEE Buff Book), 2001, 2421986 IEEE
[10]  
IEEE Recommended Pract. for Syst. Grounding of Ind. and Commercial Power Syst, 2019, 300312019 IEEE