Removal and Leakage of Environmental Tobacco Smoke from a Model Smoking Room

被引:6
作者
Wan, Man-Pun [2 ]
Wu, Chi-Li [1 ]
Chan, Tsz-Tung [1 ]
Chao, Christopher Y. H. [1 ]
Yeung, Lam-Lung [3 ]
机构
[1] Hong Kong Univ Sci & Technol, Dept Mech Engn, Kowloon, Hong Kong, Peoples R China
[2] Nanyang Technol Univ, Sch Mech & Aerosp Engn, Singapore, Singapore
[3] Hong Kong Univ Sci & Technol, Dept Chem, Hong Kong, Hong Kong, Peoples R China
关键词
environmental tobacco smoke; indoor air quality; smoking room; ultrafine particles; SECONDHAND SMOKE; NICOTINE; EXPOSURE; WORKERS; MARKER; AIR;
D O I
10.1080/15459624.2010.504432
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Experimental studies on the removal of accumulated environmental tobacco smoke (ETS) and the effectiveness of ETS leakage control were carried out in a model smoking room using carbon monoxide, nicotine, 3-ethenylpyridine, respirable suspended particulates, and ultrafine particles (UFP) as the ETS tracers. The study investigated the effectiveness of the designated smoking room, equipped with a displacement ventilation system under different ventilation rates (10-58 L/sec per person,) in removing the ETS tracers. The extent of ETS leakage through different door operating scenarios under various ventilation rates was intensively studied. In particular a manikin installed on a motorized rail was used to study the effect of human movement on the leakage of the ETS tracers. A double-door anteroom design was incorporated into the smoking room to study its effectiveness in ETS leakage prevention. It shows that at least 5 Pa of negative pressure, a fresh air supply rate 3-5 times higher than a typical office, direct air exhaust without air recirculation, and keeping the door closed are important for reducing ETS leakage. However with the smokers moving in and out and the opening of the door, noticeable leakage of ETS can occur The double-door anteroom design can improve leakage prevention. Among the five tracers, nicotine required the longest purging time to remove, after the smoking activity was stopped in the smoking room, due to its highly sorptive property. At least 4.4-6 hr of purging is needed for minimizing ETS exposure by non-smokers entering the smoking room. The peak size of particulate matter inside the smoking room is about 80 100 nm, suggesting the importance of including UFP as an indicator for monitoring the exposure and leakage of ETS. The impact of manikin movement on contaminant transport was studied, providing useful information on the effects of human activities on indoor air quality multicompartmental modeling.
引用
收藏
页码:573 / 584
页数:12
相关论文
共 21 条
[1]  
ACHUTAN C, 2009, 20050076200502013080
[2]  
[Anonymous], 2007, 6212007 ASHRAE
[3]  
ANSI/ASHRAE, 2001, 622001 ANSIASHRAE
[4]  
ASHRAE, 2004, ASHRAE standard 62-2004 ventilation for acceptable, Indoor Air Quality
[5]  
*ASTM INT, 2007, D507501 ASTM INT
[6]  
ASTM International, 2000, E74100 ASTM INT
[7]   THE ORIGINS AND PROPERTIES OF ENVIRONMENTAL TOBACCO-SMOKE [J].
BAKER, RR ;
PROCTOR, CJ .
ENVIRONMENT INTERNATIONAL, 1990, 16 (03) :231-245
[8]  
Hoegg U R, 1972, Environ Health Perspect, V2, P117, DOI 10.2307/3428103
[9]  
Jenkins R.A., 2000, CHEM ENV TOBACCO SMO
[10]   Assessment of environmental tobacco smoke exposure of Finnish restaurant workers, using 3-ethenylpyridine as marker [J].
Kuusimaki, L. ;
Peltonen, K. ;
Vainiotalo, S. .
INDOOR AIR, 2007, 17 (05) :394-403