Experimental Registration and Numerical Simulation of the Transient Overvoltages Caused by Single Phase Intermittent Arc Earth Fault in 35 kV Network With Isolated Neutral

被引:4
作者
Banjanin, Mladen S. [1 ]
Savic, Milan S. [2 ]
机构
[1] Univ East Sarajevo, Fac Elect Engn East Sarajevo, East Sarajevo 71123, Bosnia & Herceg
[2] Univ Belgrade, Fac Elect Engn, Belgrade 11000, Serbia
关键词
Surges; Voltage measurement; Ignition; Current measurement; Circuit faults; Transient analysis; Mathematical model; EMTP-ATP; experimental investigation; intermittent arc fault; isolated system neutral; medium voltage network; numerical simulation; power system transients; TEMPORARY OVERVOLTAGES; OVERHEAD DISTRIBUTION;
D O I
10.1109/TPWRD.2021.3098829
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The paper presents the results of experimental registrations and numerical simulations of the transient overvoltages caused by single phase intermittent arc earth fault in 35 kV network with isolated neutral. Experimental laboratory investigation is performed in order to implement appropriate arc fault model for arcs with low and discontinuous current. Single phase to earth arc fault is created in field in 35 kV network. Numerical model of the system is created in EMTP-ATP software. Overvoltage waveshapes and overvoltage factors are calculated and compared to measured values. Good agreement between the measured and calculated results is achieved.
引用
收藏
页码:1795 / 1802
页数:8
相关论文
共 29 条
[1]   Intermittent Fault Location in Distribution Feeders [J].
Alamuti, Mohsen Mohammadi ;
Nouri, Hassan ;
Ciric, Rade M. ;
Terzija, Vladimir .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (01) :96-103
[2]  
[Anonymous], 2010, HIGH VOLTAGE TEST TE
[3]  
[Anonymous], 2019, 6007112019 IEC
[4]  
[Anonymous], 2018, IEC 60071-2
[5]  
[Anonymous], 1997, ATP Rule Book
[6]   Application possibilities of special lightning protection systems of overhead distribution and transmission lines [J].
Banjanin, Mladen S. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2018, 100 :482-488
[7]  
Butler K. L., 1999, 199 IEEE Power Engineering Society Summer Meeting. Conference Proceedings (Cat. No.99CH36364), P408, DOI 10.1109/PESS.1999.784383
[8]   Ground Fault Temporary Overvoltages in MV Networks: Evaluation and Experimental Tests [J].
Cerretti, Alberto ;
Gatta, Fabio Massimo ;
Geri, Alberto ;
Lauria, Stefano ;
Maccioni, Marco ;
Valtorta, Giovanni .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (03) :1592-1600
[9]   Calculation of Lightning Flashover Rates of Overhead Distribution Lines Considering Direct and Indirect Strokes [J].
Chen, Jiming ;
Zhu, Mingxiao .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2014, 56 (03) :668-674
[10]   Hilbert-Transform-Based Transient/Intermittent Earth Fault Detection in Noneffectively Grounded Distribution Systems [J].
Cui, Tao ;
Dong, Xinzhou ;
Bo, Zhiqian ;
Juszczyk, Andrzej .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (01) :143-151