Numerical investigation on heat and mass transfer of slit finned tube heat exchanger with humid flue gas

被引:3
作者
Wang, Limin [1 ]
Shao, Yaru [1 ]
Tang, Chunli [2 ]
He, Yang [3 ]
Jin, Wanlong [1 ]
Che, Defu [1 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Multiphase Flow Power Engn, Xian, Peoples R China
[2] Xi An Jiao Tong Univ, Sch Human Settlements & Civil Engn, Dept Bldg Environm & Serv Engn, Xian 710049, Peoples R China
[3] Xi An Jiao Tong Univ, Sch Energy & Power Engn, State Key Lab Multiphase Flow Power Engn, Xian, Peoples R China
基金
中国国家自然科学基金;
关键词
condensation; dehumidifying condition; field synergy principle; heat and mass transfer; slit fin surface; FIELD SYNERGY PRINCIPLE; AIRSIDE PERFORMANCE; FLOW CHANNEL; ENHANCEMENT; DESIGN; CONVECTION; CONDUCTION;
D O I
10.1002/apj.2742
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
Very few studies have been reported on the fundamental mechanism analysis the augmentation of heat and mass transfer for the convection and condensation processes in the slit finned tube heat exchanger under dehumidifying conditions. By developing a 3D numerical model for the condensation of the slit finned tube heat exchanger under dehumidifying conditions, the heat and mass transfer characteristics were investigated under different the geometrical and operational parameters. The models neglecting convective mass flux or neglecting the water vapor loss can greatly enlarge the deviations of numerical results with respect to experimental data. The synergy angles are smaller in the windward and leeward sides of slits where the velocity field has a better synergy with both temperature field and the mass field. The slits on the fin not only increase the disturbance of fluid but continuously destroy the developments of thermal and mass concentration boundary layers, greatly enhancing the heat and mass transfer. The latent heat transfer is significantly greater than the sensible heat transfer, which accounts for 71.7% of the total heat transfer rate when inlet velocity is 1 m center dot s(-1) and volume fraction of water vapor is 15%. The increases in the inlet velocity, and the volume fraction of water vapor can enhance the heat and mass transfer coefficient of wet flue gas. Whereas, the increase in inlet velocity can reduce the difference of synergy for the velocity field and the temperature or mass concentration gradient field of different fin tubes.
引用
收藏
页数:15
相关论文
共 43 条
[1]  
Ayad F., 2021, APPL THERM ENG, V183
[2]   Numerical analysis of filmwise condensation in a plate fin-and-tube heat exchanger in presence of non-condensable gas [J].
Benelmir, Riad ;
Mokraoui, Salim ;
Souayed, Ali .
HEAT AND MASS TRANSFER, 2009, 45 (12) :1561-1573
[3]   Heat transfer enhancement in mini-channel heat sinks with dimples and cylindrical grooves [J].
Bi, C. ;
Tang, G. H. ;
Tao, W. Q. .
APPLIED THERMAL ENGINEERING, 2013, 55 (1-2) :121-132
[4]   Field Synergy Principle for Energy Conservation Analysis and Application [J].
Chen, Qun ;
Wang, Moran ;
Guo, Zeng-Yuan .
ADVANCES IN MECHANICAL ENGINEERING, 2010,
[5]   Numerical design of efficient slotted fin surface based on the field synergy principle [J].
Cheng, YP ;
Qu, ZG ;
Tao, WQ ;
He, YL .
NUMERICAL HEAT TRANSFER PART A-APPLICATIONS, 2004, 45 (06) :517-538
[6]   Numerical evaluation of fin performance under dehumidifying conditions [J].
Comini, G. ;
Nonino, C. ;
Savino, S. .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 2007, 129 (10) :1395-1402
[7]   Latent and sensible heat transfer in air-cooling applications [J].
Comini, G. ;
Savino, S. .
INTERNATIONAL JOURNAL OF NUMERICAL METHODS FOR HEAT & FLUID FLOW, 2007, 17 (5-6) :608-627
[8]   Modeling of conjugate conduction and heat and mass convection in tube-fin exchangers [J].
Comini, G. ;
Nonino, C. ;
Savino, S. .
INTERNATIONAL JOURNAL OF NUMERICAL METHODS FOR HEAT & FLUID FLOW, 2008, 18 (7-8) :954-968
[9]   Modeling of coupled conduction and convection in moist air cooling [J].
Comini, G. ;
Nonino, C. ;
Savino, S. .
NUMERICAL HEAT TRANSFER PART A-APPLICATIONS, 2007, 51 (01) :23-37
[10]   Thermal-performance evaluation of coolant passages with staggered arrays of pin fins [J].
D'Agaro, P. ;
Comini, G. .
HEAT AND MASS TRANSFER, 2008, 44 (07) :815-825