Examination of the performance effects of refrigerants in a multistage refrigeration cycle using advanced exergy analysis

被引:0
作者
Kaya, A. M. [1 ]
机构
[1] Bursa Uludag Univ, Dept Mech Engn, TR-16059 Bursa, Turkey
关键词
Advanced exergy; Avoidable; unavoidable; Endogenous; exogenous; Multistage refrigeration; Compression refrigeration; WORKING FLUIDS; SYSTEM; ENERGY; HEAT; PARALLEL;
D O I
10.1007/s13762-022-04227-3
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
A two-stage vapor compression refrigeration system was investigated using advanced-exergy-based analysis, which examines the effects of each component and their interactions with each other for system development. The advanced-exergy-based analysis guides how much improvement can be made on the parts of the system, examining exergy destruction in the form of endogenous/exogenous and avoidable/unavoidable parts. In addition, a parametric study was conducted and the performances of different refrigerants were evaluated to analyze the system under various operating conditions. The highest exergy destruction arises as 8.1 kW for R227ea. The total compressor works decrease 0.667 kW by changing the refrigerant from R227ea to R142b. R152a shows a preferable performance along with environmentally friendly characteristics. The condenser has the most critical improvement potential with 0.869 kW, and it accounts for 31% of the total irreversibility. It is followed by the evaporator 0.734 kW (26.2%). All exergy destruction in the evaporator falls into endogenous-part. The irreversibility of the evaporator is directly related to inner inefficiency. Coefficient of performance decreases by 40% for a condenser temperature variation from 30 to 50 degrees C. An increment in the evaporator temperature from - 15 to 0 degrees C increases coefficient of performance by 49.95%. The avoidable exergy-destruction rate can be minimized by 24.89% for that temperature variation.
引用
收藏
页码:6163 / 6182
页数:20
相关论文
共 45 条
  • [41] Adsorption-compression cascade cycles: An experimental study
    Vasta, Salvatore
    Palomba, Valeria
    La Rosa, Davide
    Mittelbach, Walter
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2018, 156 : 365 - 375
  • [42] Experimental study of the behavior of a hybrid ejector-based air-conditioning system with R134a
    Wang, Hao
    Cai, Wenjian
    Wang, Youyi
    Yan, Jia
    Wang, Lei
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2016, 112 : 31 - 40
  • [43] Conventional and advanced exergy analyses of an underwater compressed air energy storage system
    Wang, Zhiwen
    Xiong, Wei
    Ting, David S. -K.
    Carriveau, Rupp
    Wang, Zuwen
    [J]. APPLIED ENERGY, 2016, 180 : 810 - 822
  • [44] Investigation of using R134a, R1234yf and R513A as refrigerant in a heat pump
    Yildiz, A.
    Yildirim, R.
    [J]. INTERNATIONAL JOURNAL OF ENVIRONMENTAL SCIENCE AND TECHNOLOGY, 2021, 18 (05) : 1201 - 1210
  • [45] Conventional and advanced exergy analysis of parallel and series compression-ejection hybrid refrigeration system for a household refrigerator with R290
    Zhao, Hongxia
    Yuan, Tianpeng
    Gao, Jia
    Wang, Xinli
    Yan, Jia
    [J]. ENERGY, 2019, 166 : 845 - 861