The Influence of DC Component on the Creepage Discharge Paths in Oil-Pressboard Insulation Under AC-DC Combined Voltage

被引:3
作者
Zhou, Peng [1 ]
Wu, Guangning [1 ]
Gao, Bo [1 ]
Yang, Yan [1 ]
Hu, Guangcai [1 ]
Liu, Cheng [1 ]
机构
[1] Southwest Jiaotong Univ, Sch Elect Engn, Chengdu 611756, Peoples R China
来源
IEEE ACCESS | 2020年 / 8卷
关键词
Discharges (electric); Power transformer insulation; Oil insulation; Electrodes; Needles; Radio frequency; Converter transformer; AC-DC combined voltage; DC component; creepage discharge; white mark; PAPER INSULATION; SURFACE;
D O I
10.1109/ACCESS.2020.2996509
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The main dielectric medium in converter transformers is the oil-pressboard. The valve windings of converter transformers are subjected to AC-DC combined voltage. Creepage discharge is a common defect of oil-pressboard insulation. The degree of the oil-immersed pressboard (OIP) damage is directly affected by different creepage discharge paths. In this study, a needle-plate model was developed to explore different creepage discharge paths in oil-pressboard insulation under AC-DC combined voltage. A high-speed camera was used to record the developmental process of white marks on the OIP. We explored reasons behind the different creepage discharge paths under different voltage types. Results revealed that the creepage discharge path and the degree of OIP damage were influenced by the DC component. Although the damaged OIP in converter transformers may cause catastrophic flashover inside the transformers, it is difficult to replace it. This implies that transformer insulation designers should pay attention to the influence of the DC component on OIP damage. In this study, we used pulse current method to detect discharge patterns. Discharge parameters were then extracted from discharge patterns. We observed that developmental process of white marks corresponded to developmental process of discharge parameters. This suggests that creepage discharges can be diagnosed based on discharge parameters. Based on these conclusions, important information was provided for the on-line monitoring design of transformer insulation status.
引用
收藏
页码:96284 / 96293
页数:10
相关论文
共 25 条
[1]  
[Anonymous], 1997, LOAD LOSS HVDC CONV, P53
[2]  
[Anonymous], 2007, THESIS MIT U
[3]  
[Anonymous], 2015, HVDC LCC CONV TRANSF
[4]  
[Anonymous], 1998, 602431998 IEC
[5]   Influences of Temperature on Partial Discharge Behavior in Oil-paper Bounded Gas Cavity under Pulsating DC Voltage [J].
Bao, Lianwei ;
Li, Jian ;
Zhang, Jing ;
Li, Xin ;
Li, Xudong .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (03) :1482-1490
[6]   A Hybrid Task Scheduling Scheme for Heterogeneous Vehicular Edge Systems [J].
Chen, Xiao ;
Thomas, Nigel ;
Zhan, Tianming ;
Ding, Jie .
IEEE ACCESS, 2019, 7 :117088-117099
[7]  
[陈义龙 Chen Yilong], 2014, [电网技术, Power System Technology], V38, P1070
[8]   Creepage Discharge on Insulation Barriers in Aged Power Transformers [J].
Dai, J. ;
Wang, Z. D. ;
Jarman, P. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (04) :1327-1335
[9]   Online Oil Condition Monitoring Using a Partial- Discharge Signal [J].
El-Hag, Ayman H. ;
Saker, Yasser Adel ;
Shurrab, Ibrahim Yehia .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (02) :1288-1289
[10]   The Influence of Pressure on the Discharge along Oil-Paper Interface under AC Stress [J].
Hu, Guangcai ;
Wu, Guangning ;
Yu, Rui ;
Zhou, Peng ;
Gao, Bo ;
Yang, Yan ;
Liu, Kai .
ENERGIES, 2019, 12 (10)