Calculation of Minimum Approach Distances for Tools for Live-Line Working under Freezing Conditions

被引:23
作者
Ghassemi, M. [1 ]
Farzaneh, M.
机构
[1] Univ Quebec Chicoutimi, NSERC Hydroquebec UQAC Ind Chair Atmospher Icing, Chicoutimi, PQ, Canada
关键词
Minimum Approach Distance (MAD) for tools; IEEE Std. 516-2009; IEC Std. 61472-2013; cold and freezing climate regions; FRP HOT STICK; ELECTRICAL-FIELD;
D O I
10.1109/TDEI.2015.005148
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
IEEE Std. 516-2009 and IEC 61472-2013 present Minimum Approach Distance (MAD) requirements for tools to perform live maintenance safely, provided that the tool has no continuous film of moisture or measurable contamination present on its surface. However, four separate "clean" FRP hot-stick flashover incidents occurred in Canada under steady-state system conditions at the peak of the voltage negative half-cycle during cold and freezing conditions. This paper investigates IEC and IEEE methods of calculating MAD for tools employed for live working done on the geometry of the Manitoba site incidents at 500-kV. Based on cold fog tests carried out at CIGELE to reproduce these incidents, guidelines for calculating MAD in cold and freezing climate regions are proposed.
引用
收藏
页码:987 / 994
页数:8
相关论文
共 21 条
[1]  
[Anonymous], 1968, IEEE T POWER AP SYST, VPA87, P346
[2]  
[Anonymous], 2002, IEEE T POWER DELIVER, V17, P809
[3]  
[Anonymous], 614722013 IEC
[4]  
[Anonymous], 5162009 IEEE
[5]   Evaluation of and Replacement Strategies for Aged High Voltage Porcelain Suspension-Type Insulators [J].
Cherney, E. A. ;
Baker, A. C. ;
Kuffel, J. ;
Lodi, Z. ;
Phillips, A. ;
Powell, D. G. ;
Stewart, G. A. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (01) :275-282
[6]   The cold-fog test [J].
Chisholm, WA ;
Ringler, KG ;
Erven, CC ;
Green, MA ;
Melo, O ;
Tam, Y ;
Nigol, O ;
Kuffel, J ;
Boyer, A ;
Pavasars, IK ;
Macedo, FX ;
Sabiston, JK ;
Caputo, RB .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (04) :1874-1880
[7]  
EPRI, 1982, TRANSM LIN REF BOOK, p[51, 59]
[8]  
Farzaneh M., 2013, ELECT FLASHOVER TEST
[9]   IEC method of calculation of minimum approach distances for live working [J].
Gela, G ;
Hotte, PW ;
Charest, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (02) :635-640
[10]   Effects of Tower, Phase Conductors and Shield Wires on the Electrical Field around a Tower Window during Live-line Work [J].
Ghassemi, M. ;
Farzaneh, M. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (06) :3413-3420