Influence of tape's critical currents and current distributions on AC loss measurement in a multi-tape conductor
被引:12
|作者:
Ryu, K
[1
]
Hwang, SD
Kim, SW
Hahn, S
机构:
[1] Chonnam Natl Univ, Dept Elect Engn, Kwangju 500757, South Korea
[2] Korea Elect Power Corp, Taejon 305380, South Korea
[3] Korea Electrotechnol Res Inst, Chang Won, South Korea
[4] MIT, Francis Bitter Magnet Lab, Cambridge, MA USA
关键词:
AC loss measurement;
nonuniform current distribution;
short power cable;
uneven critical current;
D O I:
10.1109/TASC.2005.849204
中图分类号:
TM [电工技术];
TN [电子技术、通信技术];
学科分类号:
0808 ;
0809 ;
摘要:
AC loss is an important issue to design high temperature superconductor power cables, which consist of a number of Bi-2223 tapes wound on a former. In the cables, the tapes have intrinsically different critical currents, and they are electrically connected to each other and current leads. This makes loss measurements considerably complex, especially for short samples. In this work, we have prepared a multi-tape conductor composed of Bi-2223 tapes. The ac losses of the conductor have experimentally investigated. The loss tests indicate that the effect of critical currents of each tape on AC loss measurement in the multi-tape conductor is negligible only if currents in the tapes flow uniformly. Moreover, the measured loss of the conductor is in good agreement with the sum of the transport loss in each tape. However, in the case of nonuniform current distribution, the measured AC loss considerably depends on the current distribution parameter gamma, and the positioning of a voltage lead. Thus it should be very careful to measure the AC losses in the short power cable samples.
引用
收藏
页码:1611 / 1614
页数:4