A modified direct power control strategy allowing the connection of three-phase inverters to the grid through LCL filters

被引:167
作者
Serpa, Leonardo Augusto [1 ]
Ponnaluri, Srinivas
Barbosa, Peter Mantovanelli
Kolar, Johann Walter
机构
[1] ETH Zentrum, Swiss Fed Inst Technol, Power Elect Syst Lab, ETL H16, CH-8092 Zurich, Switzerland
[2] ABB Switzerland Ltd, TEchnol & Dev Power Elect, CH-5300 Turgi, Switzerland
[3] Asea Brown Boveri Corp Res, Power Elect Applicat, CH-5405 Baden, Switzerland
关键词
active damping; direct power control (DPC); grid-connected inverter; LCL filter;
D O I
10.1109/TIA.2007.904438
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This paper proposes a novel approach to adapt a conventional direct power control (DPC) for high-power applications, where a third-order LCL filter is frequently required. The LCL filter can cause a strong resonance and requires additional effort for system control. The application of a DPC for the control of a three-phase voltage source inverter that is connected to the grid through an filter has not yet been considered. The addition of an active damping strategy, together with a harmonic rejection control loop, to the conventional DPC is proposed and analyzed in this paper. The steady-state, as well as the dynamic performance of the proposed system, is verified with simulation results and experimental measurements.
引用
收藏
页码:1388 / 1400
页数:13
相关论文
共 10 条
[1]   A novel control to actively damp resonance in input LC filter of a three-phase voltage source converter [J].
Blasko, V ;
Kaura, V .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1997, 33 (02) :542-550
[2]  
Dahono PA, 2002, IEEE POWER ELECTRON, P1630
[3]   An improved stator flux estimation in steady-state operation for direct torque control of induction machines [J].
Idris, NRN ;
Yatim, AHM .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2002, 38 (01) :110-116
[4]  
LISERRE M, 2002, C REC IEEE IAS ANN M, V2, P1181
[5]   Virtual-flux-based direct power control of three-phase PWM rectifiers [J].
Malinowski, M ;
Kazmierkowski, MP ;
Hansen, S ;
Blaabjerg, F ;
Marques, GD .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2001, 37 (04) :1019-1027
[6]  
MALINOWSKI M, 2003, P IEEE ISIE03, V2, P831
[7]   Direct power control of PWM converter without power-source voltage sensors [J].
Noguchi, T ;
Tomiki, H ;
Kondo, S ;
Takahashi, I .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1998, 34 (03) :473-479
[8]  
Ponnaluri S, 2001, IEEE POWER ELECTRON, P1596, DOI 10.1109/PESC.2001.954347
[9]   Grid current regulation of a three-phase voltage source inverter with an LCL input filter [J].
Twining, E ;
Holmes, DG .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2003, 18 (03) :888-895
[10]   ANALYSIS OF A PWM AC TO DC VOLTAGE SOURCE CONVERTER UNDER THE PREDICTED CURRENT CONTROL WITH A FIXED SWITCHING FREQUENCY [J].
WU, RO ;
DEWAN, SB ;
SLEMON, GR .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1991, 27 (04) :756-764