Simultaneous control and protection schemes for DC multi microgrids systems

被引:35
作者
Abdali, Ali [1 ]
Noroozian, Reza [1 ]
Mazlumi, Kazem [1 ]
机构
[1] Univ Zanjan, Fac Engn, Dept Elect Engn, POB 45371-38791, Zanjan, Iran
关键词
DC microgrid (DC mu G); Hysteresis Current Control (HCC); Fault detection; Fuzzy inference system (FIS); Distributed generation (DG);
D O I
10.1016/j.ijepes.2018.06.054
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a novel simultaneous control interface and protection scheme for DC microgrids (DC mu G) interconnected systems, although the interconnections could be possible via two power electronic systems such as DC/DC converter. Each DC mu G presented in this paper is supplied by AC grid as well as battery bank unit, distributed generation (DG) unit and AC load unit. The proposed control interface is based on a developed suitable small signal model for each DC mu G that provides proper power flow control and cancellation of interactions between DC mu G. Also, the presented protection scheme for fast fault detection in DC link is based on fuzzy inference system (FIS), so that faults could be detected as quickly as possible in few milliseconds. In fact, the aim of this paper is simultaneous protection and control interface for DC multi microgrids, so that the performance of the controller and protection system is separate, yet integrated together. As such, DC multi microgrid performance under different events, such as change in active power of DGs and short circuit is not in trouble and disorder. Simulation results indicate the remarkable effectiveness of the proposed control interface and protection scheme for DC mu G interconnected systems. For validation of the capability and feasibility of FIS fault detection scheme, simulated network and protection algorithm are implemented in laboratory-scale. The implementation results demonstrate that FIS protection scheme can swiftly detect faults within a few milliseconds.
引用
收藏
页码:230 / 245
页数:16
相关论文
共 32 条
[11]   High-Speed Differential Protection for Smart DC Distribution Systems [J].
Fletcher, Steven D. A. ;
Norman, Patrick J. ;
Fong, Kenny ;
Galloway, Stuart J. ;
Burt, Graeme M. .
IEEE TRANSACTIONS ON SMART GRID, 2014, 5 (05) :2610-2617
[12]   Integrating renewable energy sources into European grids [J].
Hammons, T. J. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2008, 30 (08) :462-475
[13]   Control and load-dispatching strategies for a microgrid with a DC/AC inverter of fixed frequency [J].
Huang, Xinhong ;
Wang, Zhutian ;
Jiang, Jin .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2012, 43 (01) :1127-1136
[14]  
Ito Y, 2004, IEEE INT POWER ELEC, P1740
[15]  
JOHNSON BK, 1993, IEEE POWER ELECTRON, P759, DOI 10.1109/PESC.1993.472009
[16]   DC bus voltage control for a distributed power system [J].
Karlsson, P ;
Svensson, J .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2003, 18 (06) :1405-1412
[17]   Current control techniques for three-phase voltage-source PWM converters: A survey [J].
Kazmierkowski, MP ;
Malesani, L .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 1998, 45 (05) :691-703
[18]   A novel fault protection system using communication-assisted digital relays for AC microgrids having a multiple grounding system [J].
Lien, Keng-Yu ;
Duong Minh Bui ;
Chen, Shi-Lin ;
Zhao, Wei-Xiang ;
Chang, Yung-Ruei ;
Lee, Yih-Der ;
Jiang, Jheng-Lun .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2016, 78 :600-625
[19]   Regional protection scheme designed for low-voltage micro-grids [J].
Lin, Xiangning ;
Zhang, Rui ;
Tong, Ning ;
Li, Xianshan ;
Li, Ming ;
Yang, Dexian .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2015, 64 :526-535
[20]   Optimal Operation Mode Selection for a DC Microgrid [J].
Ma, Wann-Jiun ;
Wang, Jianhui ;
Lu, Xiaonan ;
Gupta, Vijay .
IEEE TRANSACTIONS ON SMART GRID, 2016, 7 (06) :2624-2632