AC flashover performance of different shed configurations of composite insulators under fan-shaped non-uniform pollution

被引:42
|
作者
Zhang, Zhijin [1 ]
Qiao, Xinhan [1 ]
Zhang, Yi [1 ]
Tian, Liang [1 ]
Zhang, Dongdong [1 ]
Jiang, Xingliang [1 ]
机构
[1] Chongqing Univ, Sch Elect Engn, State Key Lab Power Transmiss Equipment & Syst Se, 174 Shazheng St, Chongqing 400044, Peoples R China
来源
HIGH VOLTAGE | 2018年 / 3卷 / 03期
关键词
insulator testing; composite insulators; flashover; porcelain insulators; wind power; power transmission; composite insulator; glass insulators; AC flashover performance; shed configurations; fan-shaped nonuniform pollution; transmission lines; unidirectional wind landform; artificial pollution tests; flashover voltage; salt deposit density; creepage distance utilisation rate; LOW ATMOSPHERIC-PRESSURE; SHORT SAMPLES; DC; VOLTAGE; PORCELAIN; DESIGN; MODEL;
D O I
10.1049/hve.2018.0002
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Currently, it is founded that under unidirectional wind and certain landform, composite insulators are always fan-shaped non-uniformly polluted. In this paper, artificial pollution tests on three types of composite insulators with different shed configurations and under various fan-shaped non-uniform pollution conditions were carried out. Then the flashover performances of composite insulators, porcelain insulators and glass insulators were compared. Results indicate that there is a big difference between ac flashover performance of composite insulators under non-uninform pollution and uninform pollution. The flashover voltage of composite insulator is largely influenced by salt deposit density (SDD), the ratio of SDD of windward side to leeward side (W/L), the occupation ratio of leeward side k and the shed configurations. The relationship between SDD and U-50 still meets negative power function when composite insulator is fan-shaped non-uninform polluted. There is a reduction of 17.8-27.6% in the flashover strength when the ratio W/L of SDD decreases from 1/1 to 1/15. The shed configurations of composite insulators have great effects on the flashover performance. Composite insulators always have better withstand property compared to glass and porcelain insulators under either uniform pollution or fan-shaped non-uniform pollution.
引用
收藏
页码:199 / 206
页数:8
相关论文
共 50 条
  • [41] Investigation of Flashover Performance on 22kV RTV Coated Bushing Under Non-Uniform Coastal Pollution
    Kumar, K.
    Priya, Vishnu K.
    Vidya, Sree T.
    2018 4TH INTERNATIONAL CONFERENCE ON ELECTRICAL ENERGY SYSTEMS (ICEES), 2018, : 546 - 551
  • [42] Study on AC Pollution Flashover Performance of Composite Insulators at High altitude Sites of 2800-4500 m
    Jiang, Xingliang
    Yuan, Jihe
    Zhang, Zhijin
    Hu, Qin
    Cheng, Aijun
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2009, 16 (01) : 123 - 132
  • [43] AC Flashover Performance of 10 kV Novel Composite Insulators under Icing Conditions in Natural Environment
    Qiao, Xinhan
    Hu, Jianping
    Sundararajan, Raji
    Zhang, Zhijin
    Fang, Zhen
    Jiang, Xingliang
    2020 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (2020 IEEE CEIDP), 2020, : 172 - 175
  • [44] Improving the performance of a non-uniform field system under AC voltage
    Belhoul, Talit
    Serir, Chafiaa
    Belkaid, Abdelhakim
    Colak, Ilhami
    Mokrani, Zahra
    12TH INTERNATIONAL CONFERENCE ON SMART GRID, ICSMARTGRID 2024, 2024, : 788 - 792
  • [45] Analysis of PV module connected in different configurations under uniform and non-uniform solar radiations
    Vengatesh, R. Pon
    Rajan, S. Edward
    INTERNATIONAL JOURNAL OF GREEN ENERGY, 2016, 13 (14) : 1507 - 1516
  • [46] Flashover Process and Frequency Analysis of the Leakage Current on Insulator Model under non-Uniform Pollution Conditions
    Douar, M. A.
    Mekhaldi, A.
    Bouzidi, M. C.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (04) : 1284 - 1297
  • [47] Voltage Distribution and Flashover Performance of 220 kV Composite Insulators under Different Icing Conditions
    Lu, Jiazheng
    Xie, Pengkang
    Jiang, Zhenglong
    Fang, Zhen
    Wu, Wei
    ENERGIES, 2018, 11 (03)
  • [48] The numerical research on cavitation performance of the composite propeller under uniform and non-uniform inflow
    Li, M. M.
    Hong, Y.
    Zhang, H. L.
    Wang, R. G.
    He, X. D.
    OCEAN ENGINEERING, 2025, 322
  • [49] DC Flashover Dynamic Model of Post Insulator under Non-Uniform Pollution between Windward and Leeward Sides
    Zhang, Zhijin
    Yang, Shenghuan
    Jiang, Xingliang
    Qiao, Xinhan
    Xiang, Yingzhu
    Zhang, Dongdong
    ENERGIES, 2019, 12 (12)
  • [50] An investigation of aerodynamic performance of aeroengine fan and booster under non-uniform inlet conditions
    Qiu Z.
    Zhu Z.
    Liu X.
    Aerospace Systems, 2024, 7 (03) : 465 - 479