AC flashover performance of different shed configurations of composite insulators under fan-shaped non-uniform pollution

被引:42
|
作者
Zhang, Zhijin [1 ]
Qiao, Xinhan [1 ]
Zhang, Yi [1 ]
Tian, Liang [1 ]
Zhang, Dongdong [1 ]
Jiang, Xingliang [1 ]
机构
[1] Chongqing Univ, Sch Elect Engn, State Key Lab Power Transmiss Equipment & Syst Se, 174 Shazheng St, Chongqing 400044, Peoples R China
来源
HIGH VOLTAGE | 2018年 / 3卷 / 03期
关键词
insulator testing; composite insulators; flashover; porcelain insulators; wind power; power transmission; composite insulator; glass insulators; AC flashover performance; shed configurations; fan-shaped nonuniform pollution; transmission lines; unidirectional wind landform; artificial pollution tests; flashover voltage; salt deposit density; creepage distance utilisation rate; LOW ATMOSPHERIC-PRESSURE; SHORT SAMPLES; DC; VOLTAGE; PORCELAIN; DESIGN; MODEL;
D O I
10.1049/hve.2018.0002
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Currently, it is founded that under unidirectional wind and certain landform, composite insulators are always fan-shaped non-uniformly polluted. In this paper, artificial pollution tests on three types of composite insulators with different shed configurations and under various fan-shaped non-uniform pollution conditions were carried out. Then the flashover performances of composite insulators, porcelain insulators and glass insulators were compared. Results indicate that there is a big difference between ac flashover performance of composite insulators under non-uninform pollution and uninform pollution. The flashover voltage of composite insulator is largely influenced by salt deposit density (SDD), the ratio of SDD of windward side to leeward side (W/L), the occupation ratio of leeward side k and the shed configurations. The relationship between SDD and U-50 still meets negative power function when composite insulator is fan-shaped non-uninform polluted. There is a reduction of 17.8-27.6% in the flashover strength when the ratio W/L of SDD decreases from 1/1 to 1/15. The shed configurations of composite insulators have great effects on the flashover performance. Composite insulators always have better withstand property compared to glass and porcelain insulators under either uniform pollution or fan-shaped non-uniform pollution.
引用
收藏
页码:199 / 206
页数:8
相关论文
共 50 条
  • [31] Electrical Performance of 330-kV Composite Insulators with Different Shed Configurations under Icing Conditions
    Yin, Fanghui
    Jiang, Xingliang
    Farzaneh, Masoud
    Hu, Jianlin
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (06) : 3395 - 3404
  • [32] Effect of non-uniform pollution on the AC flashover performance of XP-160 suspension ceramic insulator string
    Zhang, Zhijin
    Liu, Xiaohuan
    Jiang, Xingliang
    Yuan, Chao
    Hu, Jianlin
    Gaodianya Jishu/High Voltage Engineering, 2013, 39 (02): : 280 - 286
  • [33] Artificial Neural Network Approach for Prediction of Leakage Current of polymeric insulator under Non-Uniform Fan-shaped Contamination
    Ghiasi, Zahra
    Faghihi, Faramarz
    Shayegani-Akmal, Amir Abbas
    ELECTRIC POWER SYSTEMS RESEARCH, 2022, 209
  • [34] Flashover Performance of Polluted Composite Insulators Under AC and Hybrid AC/DC Field Stress
    Saadati, Hassan
    Werle, Peter
    Gockenbach, Ernst
    Borsi, Hossein
    Seifert, Jens Martin
    2016 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2016, : 170 - 173
  • [35] Leakage current analysis of polymeric insulators under uniform and non-uniform pollution conditions
    Ahmadi-Joneidi, Iman
    Shayegani-Akmal, Amir Abbas
    Mohseni, Hossein
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (11) : 2947 - 2957
  • [36] Modeling of Insulator DC Pollution Flashover Under Windward/Leeward Side Non-uniform Pollution
    Zhang D.
    Ni X.
    Wang S.
    Hao S.
    Zhang Z.
    Gaodianya Jishu/High Voltage Engineering, 2020, 46 (08): : 2880 - 2889
  • [37] Flashover voltage and external insulation design for EMUs' insulators at high altitude with non-uniform distributed pollution
    Sun, Jixing
    Hu, Kaixuan
    Fan, Yongzhi
    Liu, Jiyong
    Yang, Sile
    Guo, Xugang
    Zhang, Kun
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2023, 17 (14) : 3255 - 3265
  • [38] Investigation on Flashover Voltage and Non-uniform Pollution Correction Coefficient of DC Composite Insulator
    Jiang, Xingliang
    Zhang, Zhijin
    Hu, Jianlin
    ICHVE 2008: 2008 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION, 2008, : 104 - 108
  • [39] Effects of Shed Configuration on AC Flashover Performance of Ice-covered Composite Long-rod Insulators
    Hu, Qin
    Shu, Lichun
    Jiang, Xingliang
    Sun, Caixin
    Zhang, Zhijin
    Hu, Jianlin
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2012, 19 (01) : 200 - 208
  • [40] On Discharge Inception Voltage for Insulators under Non-uniform Field with AC Voltage
    Amrani, M. L.
    Bouazabia, S.
    Fofana, I.
    Meghnefi, F.
    Jabbari, M.
    2019 INTERNATIONAL CONFERENCE ON ADVANCED ELECTRICAL ENGINEERING (ICAEE), 2019,