Water Quality as a Predictor of Legionella Positivity of Building Water Systems

被引:30
|
作者
Pierre, David [1 ]
Baron, Julianne L. [1 ]
Ma, Xiao [1 ]
Sidari, Frank P. [1 ]
Wagener, Marilyn M. [2 ]
Stout, Janet E. [1 ,3 ]
机构
[1] Special Pathogens Lab, Pittsburgh, PA 15219 USA
[2] Univ Pittsburgh, Sch Med, Pittsburgh, PA 15261 USA
[3] Univ Pittsburgh, Dept Civil & Environm Engn, Pittsburgh, PA 15261 USA
来源
PATHOGENS | 2019年 / 8卷 / 04期
关键词
Legionella; distal site positivity; hot water return line; chlorine; HPC; temperature; water management; NOSOCOMIAL LEGIONNAIRES-DISEASE; ENVIRONMENTAL SURVEILLANCE; POTABLE WATER; RISK; COLONIZATION; PNEUMOPHILA; CONTAMINATION; HOSPITALS;
D O I
10.3390/pathogens8040295
中图分类号
Q93 [微生物学];
学科分类号
071005 ; 100705 ;
摘要
Testing drinking water systems for the presence of Legionella colonization is a proactive approach to assess and reduce the risk of Legionnaires' disease. Previous studies suggest that there may be a link between Legionella positivity in the hot water return line or certain water quality parameters (temperature, free chlorine residual, etc.) with distal site Legionella positivity. It has been suggested that these measurements could be used as a surrogate for testing for Legionella in building water systems. We evaluated the relationship between hot water return line Legionella positivity and other water quality parameters and Legionella colonization in premise plumbing systems by testing 269 samples from domestic cold and hot water samples in 28 buildings. The hot water return line Legionella positivity and distal site positivity only demonstrated a 77.8% concordance rate. Hot water return line Legionella positivity compared to distal site positivity had a sensitivity of 55% and a specificity of 96%. There was poor correlation and a low positive predictive value between the hot water return line and distal outlet positivity. There was no correlation between Legionella distal site positivity and total bacteria (heterotrophic plate count), pH, free chlorine, calcium, magnesium, zinc, manganese, copper, temperature, total organic carbon, or incoming cold-water chlorine concentration. These findings suggest that hot water return line Legionella positivity and other water quality parameters are not predictive of distal site positivity and should not be used alone to determine the building's Legionella colonization rate and effectiveness of water management programs.
引用
收藏
页数:11
相关论文
共 50 条
  • [1] Evaluation of Recommended Water Sample Collection Methods and the Impact of Holding Time on Legionella Recovery and Variability from Healthcare Building Water Systems
    Hirsh, Marisa B.
    Baron, Julianne L.
    Mietzner, Sue M.
    Rihs, John D.
    Yassin, Mohamed H.
    Stout, Janet E.
    MICROORGANISMS, 2020, 8 (11) : 1 - 11
  • [2] Maintaining Legionella control in building water systems
    Sidari, Frank P., III
    Stout, Janet E.
    Duda, Scott
    Grubb, Doug
    Neuner, Alan
    JOURNAL AMERICAN WATER WORKS ASSOCIATION, 2014, 106 (10): : 24 - 32
  • [3] Identifying water quality variables most strongly influencing Legionella concentrations in building plumbing
    Julien, Ryan
    Saravi, Babak
    Nejadhashemi, Amirpouyan
    Whelton, Andrew J.
    Aw, Tiong Gim
    Mitchell, Jade
    AWWA WATER SCIENCE, 2022, 4 (01):
  • [4] A comprehensive evaluation of monochloramine disinfection on water quality, Legionella and other important microorganisms in a hospital
    Lytle, Darren A.
    Pfaller, Stacy
    Muhlen, Christy
    Struewing, Ian
    Triantafyllidou, Simoni
    White, Colin
    Hayes, Sam
    King, Dawn
    Lu, Jingrang
    WATER RESEARCH, 2021, 189
  • [5] Factors That Affect Legionella Positivity in Healthcare Building Water Systems from a Large, National Environmental Surveillance Initiative
    Gamage, Shantini D.
    Jinadatha, Chetan
    Coppin, John D.
    Kralovic, Stephen M.
    Bender, Alan
    Ambrose, Meredith
    Decker, Brooke K.
    DeVries, Aaron S.
    Goto, Michihiko
    Kowalskyj, Oleh
    Maistros, Angela L.
    Rizzo, Vincent, Jr.
    Simbartl, Loretta A.
    Watson, Richard J.
    Roselle, Gary A.
    ENVIRONMENTAL SCIENCE & TECHNOLOGY, 2022, 56 (16) : 11363 - 11373
  • [6] Inaccuracy in Legionella tests of building water systems due to sample holding time
    McCoy, William F.
    Downes, Erin L.
    Leonidas, Lesley F.
    Cain, Melissa F.
    Sherman, Daniel L.
    Chen, Kevin
    Devender, Sangeetha
    Neuille, Michael J.
    WATER RESEARCH, 2012, 46 (11) : 3497 - 3506
  • [7] Existence and control of Legionella bacteria in building water systems: A review
    Springston, John P.
    Yocavitch, Liana
    JOURNAL OF OCCUPATIONAL AND ENVIRONMENTAL HYGIENE, 2017, 14 (02) : 124 - 134
  • [8] Managing Legionella and Other Pathogenic Microorganisms in Building Water Systems
    Cotruvo, Joseph A.
    Purkiss, David
    Hazan, Stan
    Sidari, Frank P., III
    DeMarco, Peter
    LeChevallier, Mark
    JOURNAL AMERICAN WATER WORKS ASSOCIATION, 2019, 111 (02): : 54 - 59
  • [9] THE COLONIZATION OF HOT WATER SYSTEMS BY LEGIONELLA
    Hruba, Libuse
    ANNALS OF AGRICULTURAL AND ENVIRONMENTAL MEDICINE, 2009, 16 (01) : 115 - 119
  • [10] Microbial and physicochemical parameters associated with Legionella contamination in hot water recirculation systems
    Serrano-Suarez, Alejandra
    Dellunde, Jordi
    Salvado, Humbert
    Cervero-Arago, Silvia
    Mendez, Javier
    Canals, Oriol
    Blanco, Silvia
    Arcas, Antoni
    Araujo, Rosa
    ENVIRONMENTAL SCIENCE AND POLLUTION RESEARCH, 2013, 20 (08) : 5534 - 5544