Influence of the optical and geometrical properties of indoor environments for the thermal performances of chilled ceilings

被引:20
作者
Arcuri, Natale [1 ]
Bruno, Roberto [1 ]
Bevilacqua, Piero [1 ]
机构
[1] Univ Calabria, Mech Energet & Management Engn Dept, I-87036 Cosenza, Italy
关键词
Chilled ceilings; Solar heat gains; Cooling loads; Buildings dynamic simulation; RADIANT PANELS; SYSTEMS; AIR; VENTILATION;
D O I
10.1016/j.enbuild.2014.12.009
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The sizing of radiant ceilings for cooling applications requires the correct evaluation of the dynamic removal thermal loads in indoor environments. The evaluation of thermal power removed by convection, infrared radiation and direct absorption of solar radiation incident on ceiling surface, called direct water load (OWL), for systems with low thermal inertia (chilled ceilings or ceilings made by capillary pipes) has to be carried out. The latter contribution must be evaluated in an accurate way because it is not a thermal load for indoor environment and strongly modifies the thermal balance in the air-conditioned volume. In order to evaluate OWL, a parametric study developed as a function of the main optical and geometrical characteristics of the cavity has been carried out with TRNSYS code. The development of a case study has highlighted the dynamic aspects of the several contributions involved in the thermal loads removal. The obtained results have allowed the definition of a new calculation methodology to evaluate the effective solar radiation absorbed by the cavity and, subsequently, to determine the fraction of solar radiation incident on ceiling surface and removed by OWL. Its evaluation has allowed estimation of the DWL incidence on the sizing procedure of light radiant ceiling for cooling applications. (C) 2014 Elsevier B.V. All rights reserved.
引用
收藏
页码:229 / 237
页数:9
相关论文
共 23 条
  • [1] Experimental study on the cooling capacity of a radiant cooled ceiling system
    Andres-Chicote, Manuel
    Tejero-Gonzalez, Ana
    Velasco-Gomez, Eloy
    Javier Rey-Martinez, Francisco
    [J]. ENERGY AND BUILDINGS, 2012, 54 : 207 - 214
  • [2] [Anonymous], 2008, 137902008 ISO
  • [3] [Anonymous], 2003, 90502003 ISO
  • [4] ASHRAE, 2004, ASHRAE SYST EQ HDB, P61
  • [5] Causone F., 2007, P 62 IT C ATI IT THE, VI, P175
  • [6] Solar radiation and cooling load calculation for radiant systems: Definition and evaluation of the Direct Solar Load
    Causone, Francesco
    Corgnati, Stefano P.
    Filippi, Marco
    Olesen, Bjarne W.
    [J]. ENERGY AND BUILDINGS, 2010, 42 (03) : 305 - 314
  • [7] Experimental evaluation of heat transfer coefficients between radiant ceiling and room
    Causone, Francesco
    Corgnati, Stefano P.
    Filippi, Marco
    Olesen, Bjarne W.
    [J]. ENERGY AND BUILDINGS, 2009, 41 (06) : 622 - 628
  • [8] Experimental and numerical analysis of air and radiant cooling systems in offices
    Corgnati, S. P.
    Perino, M.
    Fracastoro, G. V.
    Nielsen, P. V.
    [J]. BUILDING AND ENVIRONMENT, 2009, 44 (04) : 801 - 806
  • [9] Corgnati S. P., 2000, AICARR J CDA, V7, P731
  • [10] DIGITHON: A numerical model for the thermal balance of rooms equipped with radiant systems
    De Carli, Michele
    Scarpa, Massimiliano
    Tomasi, Roberta
    Zarrella, Angelo
    [J]. BUILDING AND ENVIRONMENT, 2012, 57 : 126 - 144