The counter-flow dew point evaporative cooler: Analyzing its transient and steady-state behavior

被引:44
作者
Lin, Jie [1 ]
Duc Thuan Bui [1 ]
Wang, Ruzhu [2 ]
Chua, Kian Jon [1 ]
机构
[1] Natl Univ Singapore, Dept Mech Engn, 9 Engn Dr 1, Singapore 117575, Singapore
[2] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Shanghai 200240, Peoples R China
基金
新加坡国家研究基金会;
关键词
Counter-flow; Dew point evaporative cooling; Transient response; Pressure drop; Cooling performance; COOLING SYSTEM; PERFORMANCE ANALYSIS; MAISOTSENKO CYCLE; HEAT-EXCHANGERS; NEURAL-NETWORK; BUILDINGS; DESIGN; OPTIMIZATION;
D O I
10.1016/j.applthermaleng.2018.07.092
中图分类号
O414.1 [热力学];
学科分类号
摘要
The counter-flow dew point evaporative cooler offers a markedly improved approach to air cooling instead of the conventional vapor compression chiller. Earlier studies have focused on investigating the steady-state cooling effectiveness and energy efficiency of the evaporative cooler. However, there exists limited knowledge of the cooler's transient characteristics and flow resistance. In addition, existing cooler prototypes mostly employ a water distribution system to spray the water into the wet channel, whereas the effect of water spray remains unclear. Therefore, in this paper, we present a transient and steady-state analysis of the counter-flow dew point evaporative cooler. The channel plate temperature development after water spray was measured and analyzed. A cooler prototype was designed and engineered with a horizontal orientation according to the test results, and a 2-D mathematical model was developed to simulate its performance. The model was able to accurately predict the product air temperature, cooling effectiveness, cooling capacity and COP with a maximum discrepancy of +/- 5.0%. Key results that emerged from this study revealed that the transient responses of the channel plate and the cooler agreed well with an exponential decay function. The pressure drops for the dry and wet channels spanned 16.0-29.1 Pa and 19.9-52.3 Pa, respectively. The achieved product air temperature ranged from 15.9 to 23.3 degrees C, with a COP spanning 8.6-27.0.
引用
收藏
页码:34 / 47
页数:14
相关论文
共 43 条
  • [1] A. Standard, 2013, 552013 ASHRAE
  • [2] Amer O., 2015, International Journal of Environmental Science and Development, V6, P111, DOI DOI 10.7763/IJESD.2015.V6.571
  • [3] Theoretical study of the basic cycles for indirect evaporative air cooling
    Anisimov, Sergey
    Pandelidis, Demis
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2015, 84 : 974 - 989
  • [4] [Anonymous], 2011, THESIS U NOTTINGHAM
  • [5] [Anonymous], 2011, INT J ENERGY CLEAN E
  • [6] [Anonymous], 2009, ASHRAE HDB FUNDAMENT
  • [7] On-site experimental testing of a novel dew point evaporative cooler
    Bruno, Frank
    [J]. ENERGY AND BUILDINGS, 2011, 43 (12) : 3475 - 3483
  • [8] Achieving better energy-efficient air conditioning - A review of technologies and strategies
    Chua, K. J.
    Chou, S. K.
    Yang, W. M.
    Yan, J.
    [J]. APPLIED ENERGY, 2013, 104 : 87 - 104
  • [9] Coolerado Coolerado, 2014, M30 AIR COND BROCH
  • [10] Studying the performance of an improved dew-point evaporative design for cooling application
    Cui, X.
    Chua, K. J.
    Yang, W. M.
    Ng, K. C.
    Thu, K.
    Nguyen, V. T.