Broadband Transmission via Underground Medium-Voltage Power Lines - Part II: Capacity

被引:22
|
作者
Lazaropoulos, Athanasios G. [1 ]
Cottis, Panayiotis G. [1 ]
机构
[1] Natl Tech Univ Athens, Sch Elect & Comp Engn, Athens, Greece
关键词
Broadband over power lines (BPL); channel capacity; interoperability and intraoperability; modal analysis; power-line communications (PLC); underground medum-voltage (MV) power lines; COMMUNICATION; CHANNEL; MODEL; NETWORKS; NOISE;
D O I
10.1109/TPWRD.2010.2052113
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The end-to-end transfer function of three-phase underground medium-voltage broadband over power-lines (MV/BPL) cables with common shield and armor is determined based on a new exact version of the chain scattering matrix method. The various topologies of the underground MV grid are studied with regard to the spectral behavior of the end-to-end attenuation and to the respective capacity and are compared to the corresponding overhead cases. The numerical results reveal that broadband transmission via underground MV power lines depends drastically on the type of cables used and the topology of the underground MV grid. Also, the relaxed power injection limits and the lower noise power levels characterizing underground MV/BPL transmission counteract the extremely high inherent attenuation, making the capacity achieved compatible to that achieved in overhead MV/BPL transmission.
引用
收藏
页码:2425 / 2434
页数:10
相关论文
共 50 条
  • [1] Broadband Transmission via Underground Medium-Voltage Power Lines - Part I: Transmission Characteristics
    Lazaropoulos, Athanasios G.
    Cottis, Panayiotis G.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) : 2414 - 2424
  • [2] Investigation of transmission properties on 10-kV medium-voltage power lines - Part II: Path loss
    Yang Xiaoxian
    Zheng Tao
    Zhang Baohui
    Xu, Nucleus H.
    Li Changxin
    Tong Lixi
    IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (04) : 1886 - 1895
  • [3] Thermal analysis of the influence of harmonics on the current capacity of medium-voltage underground power cables
    Gouda, Osama E.
    El Dein, Adel Z.
    Tag-Eldin, Elsayed
    Lehtonen, Matti
    Darwish, Mohamed M. F.
    ENERGY SCIENCE & ENGINEERING, 2023, 11 (10) : 3471 - 3485
  • [4] Underground Medium-Voltage Cable Rejuvenation-Part II: Pilot Projects in the Field
    Pelissou, Serge
    St-Antoine, Serge
    IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (04) : 2605 - 2612
  • [5] CALCULATING THE MAXIMUM TRANSMISSION CAPACITY OF MEDIUM-VOLTAGE SYSTEMS
    HAUSDORF, D
    ENERGIETECHNIK, 1979, 29 (08): : 309 - 313
  • [6] Load power losses in a medium-voltage network lines
    Czepiel, Stanislaw
    PRZEGLAD ELEKTROTECHNICZNY, 2011, 87 (10): : 262 - 266
  • [7] Measurements and Modeling of Noise on 22.9-kV Medium-Voltage Underground Power Line for Broadband Power Line Communication
    Lee, Seungjoon
    Shin, Donghwan
    Kim, Yonghwa
    Lee, Jaejo
    Eom, Kihwan
    SECURITY-ENRICHED URBAN COMPUTING AND SMART GRID, 2010, 78 : 316 - +
  • [8] Transmission channel model and capacity of overhead multi-conductor medium-voltage powerlines for broadband communications
    Amirshahi, P
    Kavehrad, M
    CCNC: 2005 2ND IEEE CONSUMER COMMUNICATIONS AND NETWORKING CONFERENCE, 2005, : 354 - 358
  • [9] A Multiconductor Model of Power Line Communication in Medium-Voltage Lines
    Franek, Lesek
    Fiedler, Petr
    ENERGIES, 2017, 10 (06):
  • [10] Enhancing Reliability for Medium Voltage Underground Power Lines
    Mariut, E. L.
    Helerea, E.
    2011 7TH INTERNATIONAL SYMPOSIUM ON ADVANCED TOPICS IN ELECTRICAL ENGINEERING (ATEE), 2011,