Repair and improvement of safety for the cracked cooling tower

被引:0
|
作者
Hara, T [1 ]
Shigematsu, T [1 ]
Kato, S [1 ]
机构
[1] Tokuyama Coll Technol, Tokuyama, Yamaguchi, Japan
关键词
D O I
暂无
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The cooling tower repair systems are evaluated considering the safety and the improvement of structural strength. Two repairing systems have been ordinary adopted for the old cooling tower. One is adding the concrete layers on the shell surfaces. The other is stiffened by the R/C ring stiffeners. In this analysis, former procedure is adopted and is analyzed by focusing on the effect of the additional thickness. The finite element procedure based on the isoparametric degenerated shell is adopted to evaluate the effects of repairing the old cooling tower. Numerical parameters are the shell thickness and the amount of additional reinforcement. From the numerical analysis, the initial crack load, the reinforcement yield load and the failure load are detected and the safety of the old cooling tower is discussed.
引用
收藏
页码:315 / 321
页数:7
相关论文
共 50 条
  • [1] Advice on cooling tower and chiller repair
    AFE Facil Eng J, 1 (13):
  • [2] Safety of defected cooling tower shell
    Kasprzak, T.
    Konderla, P.
    Wasniewski, G.
    SHELL STRUCTURES: THEORY AND APPLICATIONS, VOL 2, 2010, : 295 - 298
  • [3] REPAIR AND COMPLETION OF DAMAGED COOLING-TOWER
    GOULD, PL
    GUEDELHOEFER, OC
    JOURNAL OF STRUCTURAL ENGINEERING, 1989, 115 (03) : 576 - 593
  • [4] FINITE-ELEMENT ANALYSES OF CRACKED COOLING-TOWER SHELL
    MESCHKE, G
    MANG, HA
    KOSZA, P
    JOURNAL OF STRUCTURAL ENGINEERING-ASCE, 1991, 117 (09): : 2620 - 2639
  • [5] Evaluation of safety of RC cooling tower with imperfections
    Wroblewski, R.
    Kaminski, M.
    SHELL STRUCTURES: THEORY AND APPLICATIONS, VOL 3, 2014, : 575 - 578
  • [6] TEN POINTERS TO BETTER COOLING TOWER SAFETY.
    Anon
    HAC, 1987, 58 (661): : 12 - 14
  • [7] Improvement of the thermodynamic properties in a natural-draft cooling tower
    Sirok, Brane
    Rotar, Maja
    Hocevar, Marko
    Dular, Matevz
    Smrekar, Jure
    Bajcar, Tom
    STROJNISKI VESTNIK-JOURNAL OF MECHANICAL ENGINEERING, 2007, 53 (05): : 270 - 284
  • [8] Design improvement of central cooling plant for energy saving using cooling tower water
    Vakiloroaya, Vahid
    Fakhar, Ahmad
    Samali, Bijan
    Pishghadam, Kambiz
    JOURNAL OF RENEWABLE AND SUSTAINABLE ENERGY, 2013, 5 (05)
  • [9] New retrofit method to cooling capacity improvement of mechanical draft wet cooling tower group
    Deng, Weipeng
    Sun, Fengzhong
    Chen, Kun
    Zhang, Xiaoyu
    International Journal of Heat and Mass Transfer, 2022, 188
  • [10] New retrofit method to cooling capacity improvement of mechanical draft wet cooling tower group
    Deng, Weipeng
    Sun, Fengzhong
    Chen, Kun
    Zhang, Xiaoyu
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2022, 188