Time and Frequency Characteristics of Very Fast Transient Overvoltage in Ultra High Voltage Substation

被引:24
|
作者
Ma, Guo-Ming [1 ,2 ]
Li, Cheng-Rong [1 ,2 ]
Li, Xiong [1 ,2 ]
Zhou, Hong-Yang [1 ,2 ]
Chen, Wei-Jiang [3 ]
Wang, Hao [4 ]
Li, Zhi-bing [4 ]
机构
[1] North China Elect Power Univ, Beijing Key Lab High Voltage, Key Lab Alternate Elect Power Syst Renewable Ener, 2 Beinong Rd, Beijing 102206, Peoples R China
[2] North China Elect Power Univ, EMC, 2 Beinong Rd, Beijing 102206, Peoples R China
[3] State Grid Corp China, Ultra High Voltage Dept, 86 West Changan St, Beijing 100031, Peoples R China
[4] China Elect Power Res Inst, High Voltage Res Dept, 15 Xiaoying East Rd, Beijing 100192, Peoples R China
关键词
GIS; VFTO; measurement; 1000 kV substation; S transform; time and frequency characteristics; GAS-INSULATED SWITCHGEAR; KV GIS; DISCONNECTOR; VFTO;
D O I
10.1109/TDEI.2017.005687
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Most work about the measurement of very fast transient overvoltage (VFTO) was carried out in the laboratory and test base. Because of the different GIS arrangement and power capacity, the time and frequency characteristics of VFTO in ultra high voltage (UHV) substation could be different with that obtained in the laboratory and test base. A series of VFTO measurements were carried out in two 1100 kV GIS substations to investigate the characteristics of on-site VFTO. The port-hole sensor based on surface-mounted device was chosen to measure the VFTO for its reliability and wide band-width. The whole measurement system was introduced and the schematic layout of each experiment was given. Measurement results of different switch conditions and measure points were presented for comprehensive understanding of the VFTO characteristics on site. The results indicated that the striking number during one operation was 16 (closing) and 14 (opening), similar to that obtained from test base result. Besides, single strike with front time 5.3 ns and voltage steepness 186.1 kV/ns was recorded, and the steepness was relatively higher than that gained in the test base. Moreover, the spectral analysis based on S transform was investigated to get the duration of different frequency components of VFTO waveform. Compared with the data obtained from the test base, the high frequency components of VFTO were reduced, while the lower frequency components lasted longer. The results provided references for the investigation of the electromagnetic interfere, the insulation coordination, and VFTO mitigation methods.
引用
收藏
页码:2459 / 2468
页数:10
相关论文
共 50 条
  • [41] Piecewise frequency-domain modeling of large power transformer windings for very fast transient overvoltage simulations
    Yang, Yu
    Wang, Zan-Ji
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2010, 30 (10): : 66 - 71
  • [42] A novel embedded voltage-clamped circuit for multilevel modular converters submodule to suppress very fast transient overvoltage
    Shen, Hong
    Dongye, Zhonghao
    Xiao, Mian
    Shao, Jiayi
    Zhang, Xiangyu
    Yao, Yao
    Dong, Zifan
    Qi, Lei
    HIGH VOLTAGE, 2024, 9 (06): : 1202 - 1207
  • [43] Generation mechanism and influencing factors of transient overvoltage on ultra high-voltage direct current transmission
    Yao, Weiwei
    Zhao, Jie
    Dou, Jinqiu
    Deng, Youhan
    Li, Yushu
    Liang, Yilin
    Chen, Jing
    Frontiers in Energy Research, 2025, 13
  • [44] Ground resistivity influence on the lightning overvoltage level in high voltage power substation
    Wiater, Jaroslaw M.
    XVI International Conference on Electromagnetic Disturbances : EMD 2006 - Proceedings, 2006, : 128 - 131
  • [45] Very Fast Transient Oscillation Measurement at a 750kV Substation
    Ma Guo-ming
    Li Cheng-rong
    Quan Jiang-tao
    Jiang Jian
    2009 IEEE ELECTRICAL INSULATION CONFERENCE, 2009, : 115 - 118
  • [46] Characteristics of Planar Capacitor Sensors with Dielectric Window for Very Fast Transient Overvoltage Measurement in Gas Insulated Switchgears
    Ma, Guo-ming
    Li, Cheng-rong
    Chen, Wei-jiang
    Sun, Ze-lai
    Guo, Pan-hui
    Li, Zhi-bing
    CONFERENCE RECORD OF THE 2012 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION (ISEI), 2012, : 149 - 152
  • [47] Frequency dependent and transient characteristics of substation grounding systems
    Grcev, LD
    Heimbach, M
    IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (01) : 172 - 178
  • [48] Frequency dependent and transient characteristics of substation grounding systems
    Univ `St. Cyril and Methodius', Skopje, Mk
    IEEE Trans Power Delivery, 1 (172-178):
  • [49] OVERVOLTAGE PROTECTION PROCEDURES FOR HIGH FREQUENCY HIGH VOLTAGE TRANSFORMERS
    Mendes de Souza, Diego Teruo
    Valverde, Bruno
    Pomilio, Jose Antenor
    2017 XIV BRAZILIAN POWER ELECTRONICS CONFERENCE (COBEP), 2017,
  • [50] Calculation of very fast transient overvoltage distributions in large power transformer windings
    Wang, Zan-Ji
    Yang, Yu
    Gaodianya Jishu/High Voltage Engineering, 2010, 36 (04): : 918 - 925