Development of Single Phase Liquid Cooling Solution for 3-D Silicon Modules

被引:20
作者
Tan, S. P. [1 ]
Toh, Kok Chuan [1 ,3 ]
Khan, Navas
Pinjala, D. [2 ]
Kripesh, V.
机构
[1] Nanyang Technol Univ, Temasek Labs, Singapore 637553, Singapore
[2] Inst Microelect, Microsyst Modules & Components Lab, Singapore 117585, Singapore
[3] Nanyang Technol Univ, Sch Mech & Aerosp Engn, Singapore 637553, Singapore
来源
IEEE TRANSACTIONS ON COMPONENTS PACKAGING AND MANUFACTURING TECHNOLOGY | 2011年 / 1卷 / 04期
关键词
3-D packaging; flow distribution; liquid-cooling; microchannels; thermal; PLATE HEAT-EXCHANGERS; FLOW DISTRIBUTION; PRESSURE-DROP; MICROCHANNELS;
D O I
10.1109/TCPMT.2010.2100710
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Demand for increased functionalities and the trend in product miniaturization have created new challenges for electronic packaging. The move to 3-D packages combines the benefits of small footprint packages and through-siliconvias technology to overcome the limitations. However, thermal management of such packages has become the bottleneck as cooling solutions cannot access the intermediate stacks within the package. A single phase liquid microchannel cooling solution had been designed in this paper to overcome such limitations. First, the thermal resistances within the package had been identified using a 1-D thermal network. The interconnect and silicon substrate (carrier) thermal resistances have been found to be of the same order of magnitude. Flip chip with conductive underfill is chosen as the interconnect scheme balancing the thermal, mechanical, and electrical requirements. Flow distribution in the microchannels and their impact on the thermal performance were also analyzed numerically. A dual inlet, dual outlet microchannel heatsink design with a supply plenum tapering downstream was found to provide the most even flow distribution for removing the heat away from the die. A thermal resistance of 0.15 degrees C/W and lower temperature variation on die can be obtained with such a microchannel array arrangement. Lower hydraulic losses arising from the shorter flow length and lower mean velocities also allowed the integrated pumps to operate either at smaller sizes or higher flowrates. The methodology to derive the cooling solution is presented with due consideration to the silicon fabrication processes involved.
引用
收藏
页码:536 / 544
页数:9
相关论文
共 19 条
[1]  
BASSIOUNY MK, 1984, CHEM ENG SCI, V39, P701, DOI 10.1016/0009-2509(84)80177-3
[2]   FLOW DISTRIBUTION AND PRESSURE-DROP IN PLATE HEAT-EXCHANGERS .1. U-TYPE ARRANGEMENT [J].
BASSIOUNY, MK ;
MARTIN, H .
CHEMICAL ENGINEERING SCIENCE, 1984, 39 (04) :693-700
[3]  
Bejan A, 1996, THERMAL DESIGN OPTIM
[4]  
BRUCNSCHWILER T, 2008, P ITHERM, P1114
[5]  
CULHAM JR, 2001, P IEEE CPT JUN, V2, P159
[6]  
GAMAL RA, 2003, IEEE T COMPON PACK T, V26, P610
[7]  
GARIMELLA SV, 2008, P IEEE CPT DEC, P801
[8]  
Kandlikar S. G., 2006, HEAT TRANSFER FLUID
[9]  
Kandlikar SG, 2005, P IEEE SEMICOND THER, P8
[10]  
Kays W.M., 2011, Convective heat and mass transfer