Identification and Estimation of Erroneous Transmission Line Parameters Using PMU Measurements

被引:84
作者
Asprou, Markos [1 ,2 ]
Kyriakides, Elias [1 ,2 ]
机构
[1] Univ Cyprus, Dept Elect & Comp Engn, CY-1678 Nicosia, Cyprus
[2] Univ Cyprus, KIOS Res Ctr Intelligent Syst & Networks, CY-1678 Nicosia, Cyprus
关键词
Parameter identification and estimation; phasor measurement unit; power system modeling; transmission lines; PHASOR MEASUREMENTS; UNCERTAINTY; ERRORS;
D O I
10.1109/TPWRD.2017.2648881
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The accurate knowledge of the transmission line parameters can be beneficial for several monitoring and control applications accommodated in the power system control center. Actually transmission line parameters are stored in the control center databases (assuming that they are time invariant); however, the databases might be obsolete and contain erroneous parameters. This paper proposes a methodology for identifying and estimating the erroneous transmission line parameters using measurements provided by phasor measurement units (PMUs) and estimated states provided by a state estimator. The main advantage of the proposed methodology is that for the identification of the erroneous transmission lines and the estimation of the line parameters only one PMU is required for the monitoring of the transmission line (i.e., capture measurements related to the transmission line). The proposed methodology is tested in the IEEE 14- and 118-bus systems.
引用
收藏
页码:2510 / 2519
页数:10
相关论文
共 28 条
[1]   Uncertainty modelling in power system state estimation [J].
Al-Othman, AK ;
Irving, MR .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2005, 152 (02) :233-239
[2]  
[Anonymous], C3711812011 IEEE P S
[3]  
[Anonymous], JGCM100
[4]  
[Anonymous], MOD 1133A GPS SYNCHR
[5]  
[Anonymous], 60044 IEC
[6]  
Asprou M., 2012, IEEE POW ENER SOC GE, P1
[7]  
Asprou M, 2015, IEEE POW ENER SOC GE
[8]   The Effect of Variable Weights in a WLS State Estimator Considering Instrument Transformer Uncertainties [J].
Asprou, Markos ;
Kyriakides, Elias ;
Albu, Mihaela .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2014, 63 (06) :1484-1495
[9]  
Asprou M, 2011, IEEE POW ENER SOC GE
[10]   Transmission line conductor temperature impact on state estimation accuracy [J].
Bockarjova, Marija ;
Andersson, Goeran .
2007 IEEE LAUSANNE POWERTECH, VOLS 1-5, 2007, :701-706