Experience and long term performance of 132kV overhead lines gapless-type surge arrester

被引:0
|
作者
Rawi, Iryani Mohamed [1 ]
Yahaya, Mohd Pauzi [2 ]
Ab Kadir, M. Z. A. [3 ]
Azis, Norhafiz [3 ]
机构
[1] Tenaga Nas Berhad, Engn Dept Transmisison, Kuala Lumpur, Malaysia
[2] Tenaga Nas Berhad, TNB Res, Kuala Lumpur, Malaysia
[3] Univ Putra Malaysia, Fac Engn, Ctr Electromagnet & Lightning Protect Res CELP, Serdang, Malaysia
关键词
component; Surge arrester; EGLA; Gapless TLA; OHL; Lightning; Line performance;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The Transmission Division of Tenaga Nasional Berhad (TNB), Malaysia manages and operates the 132kV, 27SkV and 500kV transmission systems that form an integrated network known as the National Grid. TNB's National Grid system spans the whole of Peninsular Malaysia that represents the backbone of the electricity industry and the Transmission Division is responsible for the safe, adequate, reliable and economical operation of the grid system in conformance to the Malaysian Grid Code. As to assure that TNB is always conformed to the Malaysian Grid Code, TNB Transmission Division together with TNB Research Sdn. Bhd. has conducted a pilot study on the use of Gapless Transmission Line Arresters (TLA) as an alternative to Gapped TLA in mid-2005. Externally Gapped Line Arrester (EGLA) has been used in TNB Transmission System since 1995 and in general it was proven that the installation of EGLA on transmission lines has improved the overhead lines performance by decreasing the number of lightning outages on the lines. However, due to high cost of the Gapped Type TLA, TNB has explored on the alternative LPS and proposed Gapless Type TLA. Three manufacturers participated in the pilot project and 148 units of Gapless TLA were installed on a 12 km 132kV lines from Balakong to Serdang Substation. The arresters and line performance were monitored intensively for a year and continuously monitored for years to come. The successful pilot study has given valuable experiences and knowledge to TNB Engineers on the selection of lightning protection equipment for overhead line system and enhancing the technical specification for the 132kV arresters.
引用
收藏
页码:517 / 520
页数:4
相关论文
共 17 条
  • [1] Modeling and simulation of a metal oxide lightning surge arrester for 132kV overhead transmission lines
    Khan, Aziz Ullah
    European Journal of Electrical Engineering, 2020, 22 (4-5) : 389 - 394
  • [2] ATP-EMTP Modeling and Performance Test of Different Type Lightning Arrester on 132kv Overhead Transmission Tower
    Islam, Md. Zoyheroul
    Rashed, Md. Rasheduzzaman
    Yusuf, Md. Salah Uddin
    2017 3RD INTERNATIONAL CONFERENCE ON ELECTRICAL INFORMATION AND COMMUNICATION TECHNOLOGY (EICT 2017), 2017,
  • [3] Analysis of Arrester Energy for 132kV Overhead Transmission Line due to Back Flashover and Shielding Failure
    Abu Bakar, Ab Halim
    Mokhlis, Hazlie
    Abd Halim, Syahirah
    Isa, Siti Sarah Mat
    Illias, Hazlee Azil
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [4] Analysis of Arrester Energy for 132kV Overhead Transmission Line due to Back Flashover and Shielding Failure
    Hassan, Nor Hidayah Nor
    Abu Bakar, Ab Halim
    Mokhlis, Hazlie
    Illias, Hazlee Azil
    2012 IEEE INTERNATIONAL CONFERENCE ON POWER AND ENERGY (PECON), 2012, : 683 - 688
  • [5] Investigation on the 132kV overhead lines lightning-related flashovers in Malaysia
    Rawi, Iryani Mohamed
    Ab Kadir, Mohd Zainal Abidin
    2015 INTERNATIONAL SYMPOSIUM ON LIGHTNING PROTECTION (XIII SIPDA), 2015, : 239 - 243
  • [6] Including Surge Arresters in the Lightning Performance Analysis of 132kV Transmission Line
    Mohajeryami, Saeed
    Doostan, Milad
    2016 IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION (T&D), 2016,
  • [7] Analysis of discharge energy on surge arrester configurations in 132 kV double circuit transmission lines
    Hassan, Nor Hidayah Nor
    Abu Bakar, Ab Halim
    Illias, Hazlee Azil
    Abd Halim, Syahirah
    Mokhlis, Hazlie
    Terzija, Vladimir
    MEASUREMENT, 2019, 139 : 103 - 111
  • [8] Modelling of 132kV Overhead Transmission Lines by Using ATP/EMTP for Shielding Failure Pattern Recognition
    Zawani, Nur
    Junainah
    Imran
    Faizuhar, Mohd
    MALAYSIAN TECHNICAL UNIVERSITIES CONFERENCE ON ENGINEERING & TECHNOLOGY 2012 (MUCET 2012), 2013, 53 : 278 - 287
  • [9] Simulation of Low Frequency Electromagnetic Fields in 132kV Overhead Transmission Lines Using 2D Finite Element Analysis
    Matias Andres, Arntzen
    Roberto Jose, Cabral
    Mario Orlando, Oliveira
    Armando, Mazzoletti M.
    2021 XIX WORKSHOP ON INFORMATION PROCESSING AND CONTROL (RPIC), 2021,
  • [10] Lightning performance improvement of the Swaziland electricity board transmission system (66kV & 132kV lines) - Results of the pilot project
    Mswane, L. M.
    Gaunt, C. T.
    IEEE Power Engineering Society Inaugural 2005 Conference and Exposition in Africa, 2005, : 364 - 370